Schneider Electric EZ9R34425 — Residual Current Breakers (RCCB/RCBO)

Schneider Electric EZ9R34425 Easy9 RCCB, 4P, 25 A, 30 mA, Ty

MPNEZ9R34425
Active

Schneider Electric Easy9 RCCB, EZ9R34425, 4P, 25 A rated, 30 mA sensitivity, Type AC earth-leakage protection, 400 V AC, clip-on DIN rail mount, IP20.

Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Jul 2026

Specifications

EZ9R34425 — Residual Current Protection
ParameterValue
Earth-leakage sensitivity (IΔn)30 mA
Earth-leakage protection class / typeType AC
Earth-leakage trip time delayInstantaneous
Residual-current tripping technologyVoltage independent
EZ9R34425 — Electrical Ratings
ParameterValue
Rated current (In)25 A
Rated operational voltage (Ue)400 V AC 50 Hz
Neutral pole positionLeft
Network typeAC
Network frequency50 Hz
Rated insulation voltage (Ui)440 V AC
Rated impulse withstand voltage (Uimp)4 kV
Device location in systemOutgoer
Electrical durabilityAC: 2000 cycles 400 V AC 50 Hz
Mechanical durability (operating cycles)5000 cycles
EZ9R34425 — Identification
ParameterValue
Product / component typeResidual current circuit breaker (RCCB)
Device short nameEasy9 RCCB
EZ9R34425 — Mechanical
ParameterValue
Mounting supportDIN rail
Mounting modeClip-on
Control typeToggle
Width in 9 mm modules8
Terminal connectionsTunnel type terminal (top or bottom) 1...35 mm² rigid Tunnel type terminal (top or bottom) 1...25 mm² flexible
Terminal tightening torque3.5 N.m top or bottom
Width72 mm
Height82 mm
Depth72 mm
EZ9R34425 — Environmental
ParameterValue
Operating ambient temperature-25...60 °C
Storage ambient temperature-40...85 °C
IP degree of protectionIP20
Pollution degree2 conforming to IEC 61008-1
Relative humidity95 % at 55 °C
Tropicalisation2
EZ9R34425 — Approvals
ParameterValue
StandardsIEC 61008-1

Product details

The Schneider Electric EZ9R34425 is a 4-pole residual current circuit breaker (RCCB) from the Easy9 range, rated 25 A with 30 mA earth-leakage sensitivity and Type AC protection.

Clip-on mounting to DIN rail, neutral on the left, 18 mm phase-to-phase connection pitch. The 72 mm width (8 x 9 mm pitches) and 72 mm depth fit standard modular enclosures; tunnel terminals accept up to 35 mm² rigid or 25 mm² flexible, torqued to 3.5 N·m.

The 25 A rated current and 500 A making/breaking capacity suit it for final sub-circuits feeding lighting or general-purpose socket outlets in 400 V three-phase systems. The 30 mA sensitivity provides personal protection against indirect contact and supplementary protection against direct contact, per IEC 61008-1. Pollution degree 2 and IP20 make it suitable for clean, dry indoor panels only — not for washdown or outdoor locations.

Frequently asked questions

Where can I buy EZ9R34425 and how do I get a price?

This part is sourced and quoted to order against an RFQ through independent distribution. Submit an RFQ for current pricing and availability.

What compliance documentation does Schneider provide for EZ9R34425?

The part is designed to IEC 61008-1. For RoHS, REACH, and other compliance documentation, refer to the manufacturer's official declarations available on request.

What is the closest alternative to EZ9R34425 in the Easy9 family?

Within the Easy9 range, the closest peer would be a 4-pole RCCB with the same 30 mA sensitivity and Type AC characteristic but a different rated current — for example, a 40 A variant. The mechanical footprint and connection pitch are identical, so swapping requires only verifying the load current matches the new rating.

MPN
EZ9R34425