Skip to main content
Schneider Electric EZ9R62263 — Residual Current Breakers (RCCB/RCBO)

Schneider Electric EZ9R62263 Easy9 RCCB, 2P, 63A, 300mA, AC

MPNEZ9R62263
Obsolete

Schneider Electric Easy9 EZ9R62263, Residual Current Circuit Breaker (RCCB), 2P, 63 A, AC type, 300 mA, IEC 61008-1.

Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Jul 2026

Specifications

EZ9R62263 — Residual Current Protection
ParameterValue
Earth-leakage sensitivity (IΔn)300 mA
Earth-leakage protection class / typeType AC
Earth-leakage trip time delayInstantaneous
EZ9R62263 — Electrical Ratings
ParameterValue
Rated current (In)63 A
Rated operational voltage (Ue)230 V AC 50 Hz
Neutral pole positionLeft
Network typeAC
Network frequency50/60 Hz
Rated impulse withstand voltage (Uimp)4 kV
Device location in systemOutgoer
Electrical durability4000 cycles
Mechanical durability (operating cycles)10000 cycles
EZ9R62263 — Identification
ParameterValue
Product / component typeResidual current circuit breaker (RCCB)
Product range / familyEasy9
EZ9R62263 — Mechanical
ParameterValue
Mounting supportDIN rail
Mounting modeClip-on
Control typeToggle
Width in 9 mm modules4
Terminal connectionsTunnel type terminal (top or bottom) 1...35 mm² rigid Tunnel type terminal (top or bottom) 1...25 mm² flexible
Terminal tightening torque3.5 N.m top or bottom
Width36 mm
Height81 mm
Depth73 mm
EZ9R62263 — Environmental
ParameterValue
Operating ambient temperature-5...60 °C
Storage ambient temperature-40...85 °C
IP degree of protectionIP20 IP40 (modular enclosure)
Relative humidity95 % at 55 °C
Tropicalisation2 conforming to IEC 60068-2-30
EZ9R62263 — Approvals
ParameterValue
StandardsIEC 61008-1

Product details

The Schneider Electric EZ9R62263 is a 2-pole residual current circuit breaker (RCCB) from the Easy9 range, rated 63 A with 300 mA earth-leakage sensitivity, Type AC (trips on sinusoidal AC fault currents).

This part is officially obsolete per the manufacturer. No successor order code is listed in the available records.

Rated operational voltage is 230 V AC at 50 Hz, with a breaking and making capacity of 630 A at 230 V per IEC 61008-1. The conditional short-circuit current is 6000 A — meaning the device can withstand a fault up to 6 kA if backed by an upstream overcurrent protective device sized per the standard. Rated impulse withstand voltage is 4 kV, which covers typical transient overvoltages in residential distribution. The tunnel-type terminals accept 1–35 mm² rigid or 1–25 mm² flexible cable, torqued to 3.5 N·m. IP20 on the body, IP40 when enclosed in a modular enclosure — standard for indoor panel installation. The part is tropicalised per IEC 60068-2-30 (damp heat cyclic), which matters for high-humidity environments.

Mounts on DIN rail via clip-on mechanism. Occupies 4 modules of 9 mm pitch (36 mm width). Neutral is on the left. The toggle control provides a contact-position indicator. Tightening torque of 3.5 N·m on the tunnel terminals — use a torque screwdriver to avoid terminal damage.

Frequently asked questions

Where can I buy EZ9R62263?

This part is sourced and quoted to order against an RFQ through independent distribution. Availability and current pricing are confirmed at quote time.

What are the key ratings of EZ9R62263?

It is a 2-pole RCCB rated 63 A, 300 mA sensitivity, Type AC, 230 V AC, with a conditional short-circuit current of 6000 A and impulse withstand of 4 kV.

What is the depth of EZ9R62263?

The depth is 73 mm.

What standards does EZ9R62263 comply with?

It complies with IEC 61008-1 and is tropicalised per IEC 60068-2-30.

MPN
EZ9R62263