Specifications

EZC100F3016 — Identification
ParameterValue
Product / component typeCircuit breaker
Range of productEasyPact
Device applicationDistribution
EZC100F3016 — Electrical
ParameterValue
Network type (AC/DC)AC DC
Rated current [In]16 A at 40 °C
Rated operational voltage [Ue]550 V AC 50/60 Hz conforming to IEC 60947-2 250 V DC conforming to IEC 60947-2
Rated insulation voltage [Ui]690 V AC 50/60 Hz conforming to IEC 60947-2
Rated impulse withstand voltage [Uimp]6 kV conforming to IEC 60947-2
Network frequency50/60 Hz
Poles description3P
EZC100F3016 — Protection & Performance
ParameterValue
Breaking capacity25 kA Icu at 220...240 V AC 50/60 Hz conforming to IEC 60947-2 5 kA Icu at 125 V DC 1P conforming to IEC 60947-2 5 kA Icu at 250 V DC 2P conforming to IEC 60947-2 5 kA Icu at 550 V AC 50/60 Hz conforming to IEC 60947-2 7.5 kA Icu at 440 V AC 50/60 Hz conforming to IEC 60947-2 10 kA Icu at 380...415 V AC 50/60 Hz conforming to IEC 60947-2
Rated service breaking capacity [Ics]2.5 kA at 125 V DC conforming to IEC 60947-2 2.5 kA at 250 V DC conforming to IEC 60947-2 2.5 kA at 550 V AC 50/60 Hz conforming to IEC 60947-2 3.75 kA at 440 V AC 50/60 Hz conforming to IEC 60947-2 5 kA at 380...415 V AC 50/60 Hz conforming to IEC 60947-2 12.5 kA at 220...240 V AC 50/60 Hz conforming to IEC 60947-2
Breaking capacity codeF
Trip unit technologyThermal-magnetic
Trip unit rating16 A at 50 °C
Trip unit nameTM-D
Protection typeOverload protection Short-circuit protection
Earth-leakage protectionWithout
Suitability for isolationYes conforming to IEC 60947-2
Utilisation categoryCategory A
Mechanical durability13000 cycles
Local signallingPositive contact indication
EZC100F3016 — Mechanical
ParameterValue
Connection pitch25 mm
Downside connectionFront
Upside connectionFront
Device short nameEasypact EZC100F
Control typeToggle
Mounting modeFixed
Mounting supportBackplate
Width75 mm
Height130 mm
Depth60 mm
EZC100F3016 — Environmental
ParameterValue
IP degree of protectionIP20 conforming to IEC 60529
IK degree of protectionIK07 conforming to EN 50102
Pollution degree3 conforming to IEC 60947
Operating ambient air temperature-25...70 °C
Storage ambient air temperature-35...85 °C
EZC100F3016 — Approvals
ParameterValue
StandardsEN/IEC 60947-1 JIS C8201-2-2 GB/T 14048.2 EN/IEC 60947-2

Product details

The EZC100F3016 is a fixed-mount, 3-pole thermal-magnetic circuit breaker from the EasyPact EZC100F series, rated 16 A at 40 °C (16 A at 50 °C with the TM-D trip unit). It carries a 25 kA Icu breaking capacity at 220–240 V AC 50/60 Hz per IEC 60947-2, and is suitable for isolation per that same standard. The kit includes the breaker with front-connect terminals, toggle control, and positive contact indication — no earth-leakage module or neutral protection built in, so plan for those separately if the circuit requires them.

At 380–415 V AC the rating drops to 10 kA Icu, and at 440 V AC to 7.5 kA Icu. For DC circuits, it manages 5 kA at 125 V DC (1-pole) or 250 V DC (2-pole). The 'F' breaking capacity code tells you this is the standard (not high-performance) variant in the EZC100 family — if your available fault current exceeds these numbers, step up to the 'N' or 'H' code.

Mounts to a backplate via fixed screws (not DIN rail). Connection pitch is 25 mm. IP20 finger-safe terminals; IK07 impact resistance.

Frequently asked questions

What is EZC100F3016's listed depth (60 mm) on this component line?

The depth is 60 mm, which fits standard MCCB panel cutouts with front-connect lugs.

MPN