Skip to main content
Schneider Electric EZC100H1016

Schneider Electric EZC100H1016 EasyPact EZC100H, 16 A, 1P, 2

MPN EZC100H1016
Active

Schneider Electric EasyPact EZC100H, circuit breaker, EZC100H1016, 16 A, 1P, 25 kA Icu at 110-130 V AC, thermal-magnetic TM-D trip unit.

Dispatch SLA24-48h Global Rush
Quality CheckOriginal Seal & Physical QC
IncotermsDAP / DDP Available
Source DocumentedChannel stated on listing & quote
Condition PhotosReal unit photos / video on request
WhatsApp AnswersFast human replies for machine-down parts
Worldwide DispatchDHL/FedEx — transit quoted per order
Independent China distributor & stockist· Listing updated Sep 2026

Specifications

EZC100H1016 key specifications
ParameterValue
Control typeToggle
Network typeDC AC
Trip unit typeThermal-magnetic
Main product or component typeCircuit breaker
Voltage125 V DC conforming to IEC 60947-2 415 V AC 50/60 Hz conforming to IEC 60947-2
Insulation voltage ui690 V AC 50/60 Hz conforming to IEC 60947-2
Breaking capacity10 kA Icu at 125 V DC 1P conforming to IEC 60947-2 25 kA Icu at 220...240 V AC 50/60 Hz conforming to IEC 60947-2 50 kA Icu at 110...130 V AC 50/60 Hz conforming to IEC 60947-2 5 kA Icu at 380...400 V AC 50/60 Hz conforming to IEC 60947-2 5 kA Icu at 415 V AC 50/60 Hz conforming to IEC 60947-2
IP ratingIP20
Terminal pitch25 mm
Connection surface topFront
Connection surface bottomFront
Temp storage max85 °C

All specifications

EZC100H1016 additional specifications
ParameterValue
Temp storage min-35 °C
Temp operating max70 °C
Temp operating min-25 °C
Storage temperature-35...85 °C
Pollution degree3 conforming to IEC 60947
Depth60 mm
Width25 mm
Height130 mm
Mechanical life cycles13000 cycles
ApplicationDistribution
Operating temperature-25...70 °C

Product details

The EZC100H1016 is a 1-pole EasyPact EZC100H circuit breaker with a thermal-magnetic TM-D trip unit rated 16 A at 50 °C. The 25 mm width per pole fits standard 25 mm pitch distribution boards — a single-pole unit occupies one module position. The breaking capacity code H delivers 25 kA Icu at 110-130 V AC and 50 kA Icu at 220-240 V AC, which covers most commercial lighting and small-load branch circuits; at 380-400 V AC it drops to 5 kA, so verify the available fault current at the installation point if feeding a 400 V line. The 10 kA Icu at 125 V DC makes it usable in DC distribution panels up to that voltage, but only for single-pole switching.

Deployment context

IP20 finger-safe terminals allow installation in enclosed panels without additional shrouding.

The toggle control provides positive contact indication — the handle position shows the contact state even if the mechanism is damaged. Mechanical durability is 13,000 cycles, which is standard for a distribution-grade breaker; not rated for frequent switching duty.

MPN
EZC100H1016