Skip to main content
Schneider Electric EZC100H1025 — Circuit Breaker Accessories

Schneider EasyPact EZC100H1025 MCCB, 25 A, 10 kA

MPNEZC100H1025
Obsolete

Schneider Electric EasyPact EZC100H, 1-pole MCCB, 25 A thermal-magnetic TM-D trip unit, 10 kA Icu at 125 V DC, IP20, backplate mount.

$47.02Ref. price · indicative, final on quote
Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Jul 2026

Specifications

EZC100H1025 — Identification
ParameterValue
Product / component typeCircuit breaker
Range of productEasyPact
Device applicationDistribution
EZC100H1025 — Electrical
ParameterValue
Network type (AC/DC)AC DC
Rated current [In]25 A at 40 °C
Rated operational voltage [Ue]125 V DC conforming to IEC 60947-2 415 V AC 50/60 Hz conforming to IEC 60947-2
Rated insulation voltage [Ui]690 V AC 50/60 Hz conforming to IEC 60947-2
Rated impulse withstand voltage [Uimp]6 kV conforming to IEC 60947-2
Network frequency50/60 Hz
Poles description1P
EZC100H1025 — Protection & Performance
ParameterValue
Breaking capacity10 kA Icu at 125 V DC 1P conforming to IEC 60947-2 25 kA Icu at 220...240 V AC 50/60 Hz conforming to IEC 60947-2 5 kA Icu at 380 V AC 50/60 Hz conforming to IEC 60947-2 5 kA Icu at 400...415 V AC 50/60 Hz conforming to IEC 60947-2 50 kA Icu at 110...130 V AC 50/60 Hz conforming to IEC 60947-2
Rated service breaking capacity [Ics]5 kA at 125 V DC conforming to IEC 60947-2 12.5 kA at 220/230/240 V AC 50/60 Hz conforming to IEC 60947-2 25 kA at 110/130 V AC 50/60 Hz conforming to IEC 60947-2 2.5 kA at 380 V AC 50/60 Hz conforming to IEC 60947-2 2.5 kA at 400/415 V AC 50/60 Hz conforming to IEC 60947-2
Breaking capacity codeH
Trip unit technologyThermal-magnetic
Trip unit rating25 A at 50 °C
Trip unit nameTM-D
Protection typeShort-circuit protection Overload protection
Earth-leakage protectionWithout
Suitability for isolationYes conforming to IEC 60947-2
Utilisation categoryCategory A
Mechanical durability13000 cycles
Local signallingPositive contact indication
EZC100H1025 — Mechanical
ParameterValue
Connection pitch25 mm
Downside connectionFront
Upside connectionFront
Device short nameEasypact EZC100H
Control typeToggle
Mounting modeFixed
Mounting supportBackplate
Width25 mm
Height130 mm
Depth60 mm
EZC100H1025 — Environmental
ParameterValue
IP degree of protectionIP20 conforming to IEC 60529
IK degree of protectionIK07 conforming to IEC 62262
Pollution degree3 conforming to IEC 60664-1 3 conforming to IEC 947-1
Operating ambient air temperature-25...70 °C
Storage ambient air temperature-35...85 °C
EZC100H1025 — Approvals
ParameterValue
StandardsJIS C8201-2-2 EN/IEC 60947-2 EN/IEC 60947-1 GB/T 14048.2

Product details

The Schneider Electric EasyPact EZC100H1025 is a 1-pole molded-case circuit breaker (MCCB) from the EZC100H series, rated 25 A at 50 °C with a thermal-magnetic TM-D trip unit. It breaks up to 10 kA Icu at 125 V DC (1-pole) per IEC 60947-2, and up to 25 kA at 220–240 V AC. The H breaking capacity code means it's sized for commercial and light industrial distribution panels where fault currents stay under 10 kA on DC circuits.

Backplate-mounted with a 25 mm connection pitch — the 25 mm width and 60 mm depth mean it occupies a single 25 mm module slot on a DIN-rail adapter plate. Front-connect terminals allow straight-in wiring from the busbar or cable. IP20 finger-safe housing suits enclosed panel use; IK07 impact rating handles tool drops during commissioning.

Certified to IEC 60947-2 and IEC 60947-1, plus JIS C8201-2-2 and GB/T 14048.2. Rated insulation voltage 690 V AC and operational voltage up to 415 V AC / 125 V DC.

Frequently asked questions

How do I get pricing and availability for EZC100H1025?

Submit an RFQ through this listing. Availability and current pricing are confirmed at quote time through independent distribution channels.

What is the breaking capacity of EZC100H1025 at 125 V DC?

10 kA Icu at 125 V DC for 1 pole, per IEC 60947-2. At 220–240 V AC it is 25 kA Icu.

What compliance documentation does Schneider provide for EZC100H1025?

The breaker is certified to IEC 60947-2, IEC 60947-1, JIS C8201-2-2, and GB/T 14048.2. Pollution degree 3 per IEC 60664-1. RoHS/REACH documentation is available from the manufacturer upon request.

MPN