Skip to main content
Schneider Electric EZC100H1045 — Circuit Breaker Accessories

Schneider Electric EZC100H1045 EasyPact EZC100H Circuit Brea

MPNEZC100H1045
Obsolete

Schneider Electric EasyPact EZC100H series, EZC100H1045, 1-pole thermal-magnetic circuit breaker, 45 A rated current, 25 kA Icu at 240 V AC, IP20, toggle control.

Source DocumentedChannel stated on listing & quote
Condition PhotosReal unit photos / video on request
WhatsApp AnswersFast human replies for machine-down parts
Worldwide DispatchDHL/FedEx — transit quoted per order
Independent China distributor & sourcing agent· Listing updated Sep 2026

Specifications

EZC100H1045 — Identification
ParameterValue
Product / component typeCircuit breaker
Range of productEasyPact
Device applicationDistribution
EZC100H1045 — Electrical
ParameterValue
Network type (AC/DC)AC DC
Rated current [In]45 A at 40 °C
Rated operational voltage [Ue]125 V DC conforming to IEC 60947-2 415 V AC 50/60 Hz conforming to IEC 60947-2
Rated insulation voltage [Ui]690 V AC 50/60 Hz conforming to IEC 60947-2
Rated impulse withstand voltage [Uimp]6 kV conforming to IEC 60947-2
Network frequency50/60 Hz
Poles description1P
EZC100H1045 — Protection & Performance
ParameterValue
Breaking capacity10 kA Icu at 125 V DC 1P conforming to IEC 60947-2 25 kA Icu at 220...240 V AC 50/60 Hz conforming to IEC 60947-2 50 kA Icu at 110...130 V AC 50/60 Hz conforming to IEC 60947-2 5 kA Icu at 380...400 V AC 50/60 Hz conforming to IEC 60947-2 5 kA Icu at 415 V AC 50/60 Hz conforming to IEC 60947-2
Rated service breaking capacity [Ics]5 kA at 125 V DC conforming to IEC 60947-2 12.5 kA at 220...240 V AC 50/60 Hz conforming to IEC 60947-2 25 kA at 110...130 V AC 50/60 Hz conforming to IEC 60947-2 2.5 kA at 380...400 V AC 50/60 Hz conforming to IEC 60947-2 2.5 kA at 415 V AC 50/60 Hz conforming to IEC 60947-2
Breaking capacity codeH
Trip unit technologyThermal-magnetic
Trip unit rating45 A at 50 °C
Trip unit nameTM-D
Protection typeShort-circuit protection Overload protection
Earth-leakage protectionWithout
Suitability for isolationYes conforming to IEC 60947-2
Utilisation categoryCategory A
Mechanical durability13000 cycles
Local signallingPositive contact indication
EZC100H1045 — Mechanical
ParameterValue
Connection pitch25 mm
Downside connectionFront
Upside connectionFront
Device short nameEasypact EZC100H
Control typeToggle
Mounting modeFixed
Mounting supportBackplate
Width25 mm
Height130 mm
Depth60 mm
EZC100H1045 — Environmental
ParameterValue
IP degree of protectionIP20 conforming to IEC 60529
IK degree of protectionIK07 conforming to EN 50102
Pollution degree3 conforming to IEC 60947
Operating ambient air temperature-25...70 °C
Storage ambient air temperature-35...85 °C
EZC100H1045 — Approvals
ParameterValue
StandardsEN/IEC 60947-1 JIS C8201-2-2 GB/T 14048.2 EN/IEC 60947-2

Product details

The Schneider Electric EZC100H1045 is a 1-pole thermal-magnetic circuit breaker from the EasyPact EZC100H series, rated 45 A at 40 °C and carrying a TM-D trip unit. It's built for distribution duty in fixed-mount backplate panels, with front-front wiring and a 25 mm pole pitch that keeps the DIN-rail layout tight. Breaking capacity varies by voltage: 25 kA Icu at 220–240 V AC, 50 kA at 110–130 V AC, 5 kA at 380–400 V AC and at 415 V AC, and 10 kA at 125 V DC single-pole — all per IEC 60947-2. That 25 kA at 240 V is the figure most panel builders will reference for a 45 A feeder on a 240/120 V split-phase service.

Compliance covers EN/IEC 60947-1, IEC 60947-2, JIS C8201-2-2, and GB/T 14048.2. IP20 finger-safe protection on the front, IK07 impact rating on the enclosure.

Mounts fixed to a backplate — no DIN-rail adapter on this one. Dimensions: 130 mm high, 25 mm wide, 60 mm deep. The 25 mm pole pitch matches standard modular breaker spacing, so it rows up neatly with other EasyPact units on the same backplate. Toggle control with positive contact indication — you can see the contact state from the handle position. Mechanical endurance is 13,000 cycles, which is typical for a distribution-grade MCCB in this class.

Frequently asked questions

What is the breaking capacity of EZC100H1045 at 240 V AC?

25 kA Icu at 220–240 V AC 50/60 Hz per IEC 60947-2. At 110–130 V AC it's 50 kA; at 380–400 V and 415 V AC it's 5 kA; at 125 V DC single-pole it's 10 kA.

What standards does EZC100H1045 comply with?

EN/IEC 60947-1, IEC 60947-2, JIS C8201-2-2, and GB/T 14048.2. Pollution degree 3 per IEC 60947, IP20 finger-safe front, IK07 impact rating.

Where can I buy EZC100H1045?

Sourced and quoted to order against an RFQ through independent distribution. Availability and current pricing confirmed at quote time — submit an RFQ for a firm price and lead time.

MPN