The EZC100H2020: Breaking capacity varies by voltage: 100 kA Icu at 110-130 V AC, 50 kA at 220-240 V AC, 30 kA at 380-415 V AC, 20 kA at 440 V AC, 10 kA at 550 V AC, and 10 kA at 125 V DC (1P) or 250 V DC (2P). That covers most industrial panel secondary-side fault levels without cascading upstream. The TM-D trip is thermal-magnetic, providing overload and short-circuit protection. Rated 20 A at 50 °C ambient, with a 20 A In at 40 °C.
Fixed backplate mount, 130 mm high, 50 mm wide, 60 mm deep. Connection pitch 25 mm. IP20 finger-safe enclosure; IK07 impact rating handles incidental tool contact in the cabinet. Toggle control with positive contact indication — the handle position reflects the actual contact state, not just the mechanism.