Skip to main content
Schneider Electric EZC100H2100 — Circuit Breaker Accessories

Schneider Electric EZC100H2100 EasyPact EZC100H 2P 100A MCCB

MPNEZC100H2100
Active

Schneider Electric EasyPact EZC100H, 2-pole molded case circuit breaker, 100 A rated current, TM-D thermal-magnetic trip unit, H breaking capacity class, front connection.

StockContact for availability
Lead timeIn Stock wk
MOQ1 pcs
Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Jul 2026
How we verify every order →

Specifications

Identification

EZC100H2100 — Identification
ParameterValue
Product / component typeCircuit breaker
Range of productEasyPact
Device applicationDistribution

Electrical

EZC100H2100 — Electrical
ParameterValue
Network type (AC/DC)AC DC
Rated current [In]100 A at 40 °C
Rated operational voltage [Ue]550 V AC 50/60 Hz conforming to IEC 60947-2 250 V DC conforming to IEC 60947-2
Rated insulation voltage [Ui]690 V AC 50/60 Hz conforming to IEC 60947-2
Rated impulse withstand voltage [Uimp]6 kV conforming to IEC 60947-2
Network frequency50/60 Hz
Poles description2P

Protection & Performance

EZC100H2100 — Protection & Performance
ParameterValue
Breaking capacity10 kA Icu at 125 V DC 1P conforming to IEC 60947-2 10 kA Icu at 250 V DC 2P conforming to IEC 60947-2 10 kA Icu at 550 V AC 50/60 Hz conforming to IEC 60947-2 100 kA Icu at 110...130 V AC 50/60 Hz conforming to IEC 60947-2 20 kA Icu at 440 V AC 50/60 Hz conforming to IEC 60947-2 30 kA Icu at 380 V AC 50/60 Hz conforming to IEC 60947-2 30 kA Icu at 400...415 V AC 50/60 Hz conforming to IEC 60947-2 50 kA Icu at 220...240 V AC 50/60 Hz conforming to IEC 60947-2
Rated service breaking capacity [Ics]15 kA at 380 V AC 50/60 Hz conforming to IEC 60947-2 5 kA at 125 V DC conforming to IEC 60947-2 5 kA at 250 V DC conforming to IEC 60947-2 50 kA at 110/130 V AC 50/60 Hz conforming to IEC 60947-2 5 kA at 440 V AC 50/60 Hz conforming to IEC 60947-2 2.5 kA at 550 V AC 50/60 Hz conforming to IEC 60947-2 7.5 kA at 400/415 V AC 50/60 Hz conforming to IEC 60947-2 25 kA at 220/230/240 V AC 50/60 Hz conforming to IEC 60947-2
Breaking capacity codeH
Trip unit technologyThermal-magnetic
Trip unit rating100 A at 50 °C
Trip unit nameTM-D
Protection typeOverload protection Short-circuit protection
Earth-leakage protectionWithout
Suitability for isolationYes conforming to IEC 60947-2
Utilisation categoryCategory A
Mechanical durability13000 cycles
Local signallingPositive contact indication

Mechanical

EZC100H2100 — Mechanical
ParameterValue
Connection pitch25 mm
Downside connectionFront
Upside connectionFront
Device short nameEasypact EZC100H
Control typeToggle
Mounting modeFixed
Mounting supportBackplate
Width50 mm
Height130 mm
Depth60 mm

Environmental

EZC100H2100 — Environmental
ParameterValue
IP degree of protectionIP20 conforming to IEC 60529
IK degree of protectionIK07 conforming to IEC 62262
Pollution degree3 conforming to IEC 60664-1 3 conforming to IEC 947-1
Operating ambient air temperature-25...70 °C
Storage ambient air temperature-35...85 °C

Approvals

EZC100H2100 — Approvals
ParameterValue
StandardsEN/IEC 60947-1 GB/T 14048.2 JIS C8201-2-2 EN/IEC 60947-2

Product details

The Schneider Electric EZC100H2100 is a 2-pole molded case circuit breaker (MCCB) from the EasyPact EZC100H series, rated 100 A at 40 °C with a TM-D thermal-magnetic trip unit that provides overload and short-circuit protection in a single compact package. Its H breaking capacity class delivers 10 kA Icu at 125 V DC (1P), 10 kA at 250 V DC (2P), 10 kA at 550 V AC, 20 kA at 440 V AC, 30 kA at 400–415 V AC, 50 kA at 220–240 V AC, and 100 kA at 110–130 V AC — all per IEC 60947-2, so the same breaker covers a wide range of fault levels across global supply voltages.

Standards and environment

Designed to EN/IEC 60947-1, GB/T 14048.2, JIS C8201-2-2, and EN/IEC 60947-2 — covering global industrial control and switchgear requirements for distribution applications. Operates from -25 °C to 70 °C and stores from -35 °C to 85 °C; pollution degree 3 per IEC 60664-1 (conductive pollution or dry non-conductive that becomes conductive) — typical for factory-floor panel environments. Mechanical durability rated at 13,000 cycles, utilisation category A (non-frequent switching), and no integrated earth-leakage or neutral protection — those are external add-ons.

Frequently asked questions

What is EZC100H2100's breaking capacity at 400 V AC?

At 400–415 V AC 50/60 Hz the EZC100H2100 delivers 30 kA Icu per IEC 60947-2.

MPN
EZC100H2100