Skip to main content
Schneider Electric EZC100H3015 — Circuit Breaker Accessories

Schneider Electric EZC100H3015 EasyPact EZC100H Circuit Brea

MPNEZC100H3015
Active

Schneider Electric EasyPact EZC100H series, thermal-magnetic MCCB, 3P, 15 A, TM-D trip unit, 10–100 kA breaking capacity, IP20, backplate mount.

$58.77Ref. price · indicative, final on quote
StockContact for availability
Lead timeIn Stock wk
MOQ1 pcs
Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Jul 2026
How we verify every order →

Specifications

Identification

EZC100H3015 — Identification
ParameterValue
Product / component typeCircuit breaker
Range of productEasyPact
Device applicationDistribution

Electrical

EZC100H3015 — Electrical
ParameterValue
Network type (AC/DC)AC DC
Rated current [In]15 A at 40 °C
Rated operational voltage [Ue]550 V AC 50/60 Hz conforming to IEC 60947-2 250 V DC conforming to IEC 60947-2
Rated insulation voltage [Ui]690 V AC 50/60 Hz conforming to IEC 60947-2
Rated impulse withstand voltage [Uimp]6 kV conforming to IEC 60947-2
Network frequency50/60 Hz
Poles description3P

Protection & Performance

EZC100H3015 — Protection & Performance
ParameterValue
Breaking capacity10 kA Icu at 125 V DC 1P conforming to IEC 60947-2 10 kA Icu at 250 V DC 2P conforming to IEC 60947-2 10 kA Icu at 550 V AC 50/60 Hz conforming to IEC 60947-2 100 kA Icu at 110...130 V AC 50/60 Hz conforming to IEC 60947-2 100 kA Icu at 220...240 V AC 50/60 Hz conforming to IEC 60947-2 20 kA Icu at 440 V AC 50/60 Hz conforming to IEC 60947-2 30 kA Icu at 380 V AC 50/60 Hz conforming to IEC 60947-2 30 kA Icu at 400...415 V AC 50/60 Hz conforming to IEC 60947-2
Rated service breaking capacity [Ics]15 kA at 380 V AC 50/60 Hz conforming to IEC 60947-2 5 kA at 125 V DC conforming to IEC 60947-2 5 kA at 250 V DC conforming to IEC 60947-2 50 kA at 110/130 V AC 50/60 Hz conforming to IEC 60947-2 50 kA at 220/230/240 V AC 50/60 Hz conforming to IEC 60947-2 5 kA at 440 V AC 50/60 Hz conforming to IEC 60947-2 2.5 kA at 550 V AC 50/60 Hz conforming to IEC 60947-2 7.5 kA at 400/415 V AC 50/60 Hz conforming to IEC 60947-2
Breaking capacity codeH
Trip unit technologyThermal-magnetic
Trip unit rating15 A at 50 °C
Trip unit nameTM-D
Protection typeShort-circuit protection Overload protection
Earth-leakage protectionWithout
Suitability for isolationYes conforming to IEC 60947-2
Utilisation categoryCategory A
Mechanical durability13000 cycles
Local signallingPositive contact indication

Mechanical

EZC100H3015 — Mechanical
ParameterValue
Connection pitch25 mm
Downside connectionFront
Upside connectionFront
Device short nameEasypact EZC100H
Control typeToggle
Mounting modeFixed
Mounting supportBackplate
Width75 mm
Height130 mm
Depth60 mm

Environmental

EZC100H3015 — Environmental
ParameterValue
IP degree of protectionIP20 conforming to IEC 60529
IK degree of protectionIK07 conforming to IEC 62262
Pollution degree3 conforming to IEC 60664-1 3 conforming to IEC 947-1
Operating ambient air temperature-25...70 °C
Storage ambient air temperature-35...85 °C

Approvals

EZC100H3015 — Approvals
ParameterValue
StandardsEN/IEC 60947-1 JIS C8201-2-2 EN/IEC 60947-2 GB/T 14048.2

Product details

The Schneider Electric EZC100H3015 is a 3-pole thermal-magnetic circuit breaker from the EasyPact EZC100H series, rated 15 A at 40 °C with a TM-D trip unit. It carries a 10 kA Icu at 550 V AC and 100 kA Icu at 240 V AC, making it suitable for distribution panels where high fault current headroom is needed on the 240 V side.

The H breaking capacity code delivers 100 kA Icu at 110–240 V AC, 30 kA at 380–415 V, and 20 kA at 440 V. At 550 V AC it still holds 10 kA. On the DC side, it is rated 10 kA at 125 V DC (1P) and 250 V DC (2P). These figures let the breaker coordinate downstream in a distribution panel where the upstream transformer or main breaker supplies high prospective fault current.

Fixed backplate mounting, front connection both top and bottom. The 60 mm depth and 75 mm width fit standard distribution board cutouts; connection pitch is 25 mm. IP20 finger-safe terminals and IK07 impact resistance cover panel-side handling.

Frequently asked questions

Where can I buy EZC100H3015 and how do I get a price?

Sourced and quoted to order against an RFQ through independent distribution; availability and current pricing confirmed at quote time.

What is the breaking capacity of EZC100H3015 at 240 V?

100 kA Icu at 220–240 V AC 50/60 Hz per IEC 60947-2.

What compliance standards does EZC100H3015 meet?

It conforms to EN/IEC 60947-1, EN/IEC 60947-2, JIS C8201-2-2, and GB/T 14048.2.

MPN