Schneider Electric EZC100H4050 — Circuit Breaker Accessories

Schneider Electric EZC100H4050 EasyPact EZC100H 50A 4P Circu

MPNEZC100H4050
Active

Schneider Electric EasyPact EZC100H, circuit breaker, 50 A, 4P, thermal-magnetic TM-D trip unit, 30 kA Icu at 400 V AC, IP20, fixed mounting.

$76.41Ref. price · indicative, final on quote
StockContact for availability
Lead timeIn Stock wk
MOQ1 pcs
Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Jul 2026
How we verify every order →

Specifications

Identification

EZC100H4050 — Identification
ParameterValue
Product / component typeCircuit breaker
Range of productEasyPact
Device applicationDistribution

Electrical

EZC100H4050 — Electrical
ParameterValue
Network type (AC/DC)AC DC
Rated current [In]50 A at 40 °C
Rated operational voltage [Ue]550 V AC 50/60 Hz conforming to IEC 60947-2 250 V DC conforming to IEC 60947-2
Rated insulation voltage [Ui]690 V AC 50/60 Hz conforming to IEC 60947-2
Rated impulse withstand voltage [Uimp]6 kV conforming to IEC 60947-2
Network frequency50/60 Hz
Poles description4P

Protection & Performance

EZC100H4050 — Protection & Performance
ParameterValue
Breaking capacity10 kA Icu at 125 V DC 1P conforming to IEC 60947-2 10 kA Icu at 250 V DC 2P conforming to IEC 60947-2 10 kA Icu at 550 V AC 50/60 Hz conforming to IEC 60947-2 100 kA Icu at 110...130 V AC 50/60 Hz conforming to IEC 60947-2 20 kA Icu at 440 V AC 50/60 Hz conforming to IEC 60947-2 50 kA Icu at 220...240 V AC 50/60 Hz conforming to IEC 60947-2 30 kA Icu at 380...400 V AC 50/60 Hz conforming to IEC 60947-2 30 kA Icu at 415 V AC 50/60 Hz conforming to IEC 60947-2
Rated service breaking capacity [Ics]5 kA at 125 V DC conforming to IEC 60947-2 5 kA at 250 V DC conforming to IEC 60947-2 5 kA at 440 V AC 50/60 Hz conforming to IEC 60947-2 2.5 kA at 550 V AC 50/60 Hz conforming to IEC 60947-2 15 kA at 380...400 V AC 50/60 Hz conforming to IEC 60947-2 25 kA at 220...240 V AC 50/60 Hz conforming to IEC 60947-2 50 kA at 110...130 V AC 50/60 Hz conforming to IEC 60947-2 7.5 kA at 415 V AC 50/60 Hz conforming to IEC 60947-2
Breaking capacity codeH
Trip unit technologyThermal-magnetic
Trip unit rating50 A at 50 °C
Trip unit nameTM-D
Protection typeShort-circuit protection Overload protection
Earth-leakage protectionWithout
Suitability for isolationYes conforming to IEC 60947-2
Utilisation categoryCategory A
Mechanical durability13000 cycles
Local signallingPositive contact indication

Mechanical

EZC100H4050 — Mechanical
ParameterValue
Connection pitch25 mm
Downside connectionFront
Upside connectionFront
Device short nameEasypact EZC100H
Control typeToggle
Mounting modeFixed
Mounting supportBackplate
Width100 mm
Height130 mm
Depth60 mm

Environmental

EZC100H4050 — Environmental
ParameterValue
IP degree of protectionIP20 conforming to IEC 60529
IK degree of protectionIK07 conforming to EN 50102
Pollution degree3 conforming to IEC 60947
Operating ambient air temperature-25...70 °C
Storage ambient air temperature-35...85 °C

Approvals

EZC100H4050 — Approvals
ParameterValue
StandardsEN/IEC 60947-2 GB/T 14048.2 EN/IEC 60947-1 JIS C8201-2-2

Product details

It carries a TM-D trip unit — fixed thermal and magnetic settings, no adjustments — so it's a straight swap-in for a line that's already coordinated. The breaking capacity hits 30 kA Icu at 400 V AC 50/60 Hz per IEC 60947-2, which covers most industrial panel SCCR requirements without stepping up to a higher frame.

At 240 V AC it jumps to 50 kA Icu, and at 125 V DC single-pole it's 10 kA. The 4-pole version (EZC100H4050) protects three phases with a solid-neutral pass-through — no neutral protection, so it's meant for three-phase loads where the neutral carries only imbalance current. IP20 means finger-safe but not sealed — mount it inside a panel with at least an IP54 enclosure if there's washdown or dust.

Fixed backplate mounting — no DIN-rail clip on this frame. You bolt it to a mounting plate in the enclosure. Connection pitch is 25 mm, front-connected both line and load sides. Toggle handle gives positive contact indication, so you can visually confirm the contacts are open or closed without a meter. It's a Category A breaker (no intentional short-time delay), so coordination with downstream breakers relies on the instantaneous trip characteristic.

Frequently asked questions

Where can I buy EZC100H4050 and how do I get a price?

This part is sourced and quoted to order against an RFQ through independent distribution. Submit an RFQ for current pricing and availability.

What is the closest alternative to EZC100H4050 in the EasyPact family?

The EasyPact EZC100H series shares the same frame size and trip-unit options. A 50 A 4P with an EZC100F frame (25 kA at 400 V) would be a lower-breaking-capacity sibling if your SCCR allows it; the EZC100N frame (50 kA at 400 V) steps up for higher fault duty. Both are the same physical footprint and TM-D trip family.

What compliance documentation does Schneider provide for EZC100H4050?

The breaker is certified to EN/IEC 60947-2, GB/T 14048.2, and JIS C8201-2-2. It carries IEC 60947-2 isolation suitability marking. RoHS and REACH declarations are standard Schneider documentation available on request.

MPN