The Schneider Electric EZC100N1016 is a 1-pole EasyPact EZC100N circuit breaker with a thermal-magnetic TM-D trip unit rated 16 A at 50 °C. It provides short-circuit and overload protection for distribution circuits. The breaker is designed for fixed backplate mounting with front connections, and uses a toggle for manual control. Rated operational voltage covers 415 V AC 50/60 Hz and 125 V DC, with an insulation voltage of 690 V AC. Breaking capacity reaches 25 kA Icu at 110-130 V AC, 18 kA at 220-240 V AC, and 5 kA at 125 V DC (1-pole). This makes it suitable for branch-circuit protection in panelboards and distribution boards where moderate fault levels are expected. The breaker carries IP20 protection (finger-safe terminals) and IK07 impact resistance. It is certified for isolation per IEC 60947-2, meaning it can be used as a disconnecting means when locked off.
Integration notes
Width of 25 mm and depth of 60 mm fit standard backplate layouts. The 25 mm connection pitch matches common terminal-block spacing. Front connections simplify wiring in tight enclosures. Positive contact indication provides visual confirmation of the contact position. Mechanical durability of 13,000 cycles is adequate for distribution duty where switching is infrequent.