Schneider EasyPact EZC100N1025 25A 1P MCCB, 25 kA Icu

MPNEZC100N1025
Active

Schneider Electric EasyPact EZC100N, 1-pole MCCB, 25 A TM-D trip unit, 25 kA Icu at 110-130 V AC, 18 kA at 240 V AC, 2.5 kA at 415 V AC, IEC 60947-2.

$59.95Ref. price · indicative, final on quote
Source DocumentedChannel stated on listing & quote
Condition PhotosReal unit photos / video on request
WhatsApp AnswersFast human replies for machine-down parts
Worldwide DispatchDHL/FedEx — transit quoted per order
Independent China distributor & sourcing agent· Listing updated Sep 2026

Specifications

EZC100N1025 — Identification
ParameterValue
Product / component typeCircuit breaker
Device applicationDistribution
EZC100N1025 — Mechanical
ParameterValue
Height130 mm
Width25 mm
Depth60 mm
EZC100N1025 — Electrical
ParameterValue
[In] rated current25 A at 40 °C
Breaking capacity25 kA Icu at 110...130 V AC 50/60 Hz conforming to IEC 60947-2 5 kA Icu at 125 V DC 1P conforming to IEC 60947-2 18 kA Icu at 220...240 V AC 50/60 Hz conforming to IEC 60947-2 2.5 kA Icu at 380 V AC 50/60 Hz conforming to IEC 60947-2 2.5 kA Icu at 400...415 V AC 50/60 Hz conforming to IEC 60947-2
[Ics] rated service breaking capacity12.5 kA at 110/130 V AC 50/60 Hz conforming to IEC 60947-2 2.5 kA at 125 V DC conforming to IEC 60947-2 9 kA at 220/230/240 V AC 50/60 Hz conforming to IEC 60947-2 1.25 kA at 380 V AC 50/60 Hz conforming to IEC 60947-2 1.25 kA at 400/415 V AC 50/60 Hz conforming to IEC 60947-2
[Ue] rated operational voltage125 V DC conforming to IEC 60947-2 415 V AC 50/60 Hz conforming to IEC 60947-2
[Ui] rated insulation voltage690 V AC 50/60 Hz conforming to IEC 60947-2
EZC100N1025 — Specifications
ParameterValue
Poles description1P
Trip unit nameTM-D
Trip unit technologyThermal-magnetic
Device short nameEasypact EZC100N
StandardsJIS C8201-2-2 EN/IEC 60947-2 GB/T 14048.2 EN/IEC 60947-1

Product details

The Schneider Electric EasyPact EZC100N1025 is a 1-pole (1P) moulded-case circuit breaker (MCCB) from the EasyPact EZC100N series, fitted with a TM-D thermal-magnetic trip unit rated at 25 A at 50 °C. Breaking capacity (Icu) reaches 25 kA at 110-130 V AC, 18 kA at 220-240 V AC, and 2.5 kA at 400-415 V AC — all per IEC 60947-2. At 125 V DC, 1-pole configuration delivers 5 kA Icu. Rated insulation voltage (Ui) is 690 V AC, and rated operational voltage (Ue) covers 415 V AC and 125 V DC. The breaker is certified for isolation per IEC 60947-2, meaning it provides a visible-break isolation function when open. Pollution degree 3 (IEC 60664-1) suits it for typical panel environments where conductive pollution may occur.

Connection pitch is 25 mm, matching the 25 mm width per pole — a standard 1-module footprint for DIN-rail-compatible MCCBs. Depth is 60 mm, height 130 mm. IP20 finger-safe protection on the front face; IK07 impact resistance per IEC 62262. The toggle actuator provides positive contact indication, so the operator can visually confirm the contact position.

Designed and tested to JIS C8201-2-2, EN/IEC 60947-2, GB/T 14048.2, and EN/IEC 60947-1. The IEC 60947-2 certification covers low-voltage switchgear and controlgear — specifically circuit-breaker performance, breaking capacity, and isolation function. Mechanical durability is rated at 13,000 cycles. No earth-leakage protection module is integrated; neutral protection is not provided (1P, no neutral pole).

Frequently asked questions

What are the key ratings of the EZC100N1025?

Rated current 25 A at 40 °C (25 A at 50 °C on the TM-D trip unit). Breaking capacity 25 kA Icu at 110-130 V AC, 18 kA at 220-240 V AC, 2.5 kA at 400-415 V AC, and 5 kA at 125 V DC. Rated insulation voltage 690 V AC, operational voltage 415 V AC / 125 V DC. 1 pole, thermal-magnetic trip.

Where can I buy the EZC100N1025?

The EZC100N1025 is sourced and quoted to order against an RFQ through independent distribution. Availability and current pricing are confirmed at quote time.

What compliance documentation does Schneider provide for EZC100N1025?

The breaker is certified to EN/IEC 60947-2, JIS C8201-2-2, and GB/T 14048.2. It carries an IP20 protection rating and IK07 impact resistance. Specific RoHS/REACH/UL documentation should be requested at quote time as it varies by manufacturing batch.

MPN