Schneider Electric EZC100N1030 — Circuit Breaker Accessories

Schneider EasyPact EZC100N1030 30 A 1P MCB, 25 kA Icu

MPNEZC100N1030
Obsolete

Schneider Electric EasyPact EZC100N, circuit breaker, 1P, 30 A, thermal-magnetic TM-D trip unit, 25 kA Icu at 110-130 V AC, 18 kA at 240 V AC, IP20, EN/IEC 60947-2.

$39.96Ref. price · indicative, final on quote
Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Jul 2026

Specifications

EZC100N1030 — Identification
ParameterValue
Product / component typeCircuit breaker
Range of productEasyPact
Device applicationDistribution
EZC100N1030 — Electrical
ParameterValue
Network type (AC/DC)AC DC
Rated current [In]30 A at 40 °C
Rated operational voltage [Ue]125 V DC conforming to IEC 60947-2 415 V AC 50/60 Hz conforming to IEC 60947-2
Rated insulation voltage [Ui]690 V AC 50/60 Hz conforming to IEC 60947-2
Rated impulse withstand voltage [Uimp]6 kV conforming to IEC 60947-2
Network frequency50/60 Hz
Poles description1P
EZC100N1030 — Protection & Performance
ParameterValue
Breaking capacity25 kA Icu at 110...130 V AC 50/60 Hz conforming to IEC 60947-2 5 kA Icu at 125 V DC 1P conforming to IEC 60947-2 18 kA Icu at 220...240 V AC 50/60 Hz conforming to IEC 60947-2 2.5 kA Icu at 380 V AC 50/60 Hz conforming to IEC 60947-2 2.5 kA Icu at 400...415 V AC 50/60 Hz conforming to IEC 60947-2
Rated service breaking capacity [Ics]12.5 kA at 110/130 V AC 50/60 Hz conforming to IEC 60947-2 2.5 kA at 125 V DC conforming to IEC 60947-2 9 kA at 220/230/240 V AC 50/60 Hz conforming to IEC 60947-2 1.25 kA at 380 V AC 50/60 Hz conforming to IEC 60947-2 1.25 kA at 400/415 V AC 50/60 Hz conforming to IEC 60947-2
Breaking capacity codeN
Trip unit technologyThermal-magnetic
Trip unit rating30 A at 50 °C
Trip unit nameTM-D
Protection typeShort-circuit protection Overload protection
Earth-leakage protectionWithout
Suitability for isolationYes conforming to IEC 60947-2
Utilisation categoryCategory A
Mechanical durability13000 cycles
Local signallingPositive contact indication
EZC100N1030 — Mechanical
ParameterValue
Connection pitch25 mm
Downside connectionFront
Upside connectionFront
Device short nameEasypact EZC100N
Control typeToggle
Mounting modeFixed
Mounting supportBackplate
Width25 mm
Height130 mm
Depth60 mm
EZC100N1030 — Environmental
ParameterValue
IP degree of protectionIP20 conforming to IEC 60529
IK degree of protectionIK07 conforming to IEC 62262
Pollution degree3 conforming to IEC 60664-1 3 conforming to IEC 947-1
Operating ambient air temperature-25...70 °C
Storage ambient air temperature-35...85 °C
EZC100N1030 — Approvals
ParameterValue
StandardsEN/IEC 60947-2 EN/IEC 60947-1 GB/T 14048.2 JIS C8201-2-2

Product details

The 25 kA Icu at 110-130 V AC (18 kA at 240 V AC, 2.5 kA at 400-415 V AC) gives you the interrupting capacity to handle moderate fault levels without cascading upstream — the N breaking capacity code positions it between standard and high-performance in the EasyPact range.

Certified to EN/IEC 60947-2, EN/IEC 60947-1, GB/T 14048.2, and JIS C8201-2-2. IP20 finger-safe terminals; IK07 impact resistance per IEC 62262.

Frequently asked questions

What is the breaking capacity of EZC100N1030 at 240 V AC?

18 kA Icu at 220-240 V AC 50/60 Hz per IEC 60947-2. At 400-415 V AC it drops to 2.5 kA Icu.

MPN