Skip to main content
Schneider Electric EZC100N1040 — Circuit Breaker Accessories

Schneider Electric EZC100N1040 EasyPact EZC100N Circuit Brea

MPNEZC100N1040
Obsolete

Schneider Electric EasyPact EZC100N, EZC100N1040, 1-pole circuit breaker, 40 A rated current, thermal-magnetic TM-D trip unit, breaking capacity 25 kA at 110-130 V AC, fixed mounting, IP20.

$39.96Ref. price · indicative, final on quote
Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Jul 2026

Specifications

EZC100N1040 — Identification
ParameterValue
Product / component typeCircuit breaker
Range of productEasyPact
Device applicationDistribution
EZC100N1040 — Electrical
ParameterValue
Network type (AC/DC)AC DC
Rated current [In]40 A at 40 °C
Rated operational voltage [Ue]125 V DC conforming to IEC 60947-2 415 V AC 50/60 Hz conforming to IEC 60947-2
Rated insulation voltage [Ui]690 V AC 50/60 Hz conforming to IEC 60947-2
Rated impulse withstand voltage [Uimp]6 kV conforming to IEC 60947-2
Network frequency50/60 Hz
Poles description1P
EZC100N1040 — Protection & Performance
ParameterValue
Breaking capacity25 kA Icu at 110...130 V AC 50/60 Hz conforming to IEC 60947-2 5 kA Icu at 125 V DC 1P conforming to IEC 60947-2 18 kA Icu at 220...240 V AC 50/60 Hz conforming to IEC 60947-2 2.5 kA Icu at 380 V AC 50/60 Hz conforming to IEC 60947-2 2.5 kA Icu at 400...415 V AC 50/60 Hz conforming to IEC 60947-2
Rated service breaking capacity [Ics]12.5 kA at 110/130 V AC 50/60 Hz conforming to IEC 60947-2 2.5 kA at 125 V DC conforming to IEC 60947-2 9 kA at 220/230/240 V AC 50/60 Hz conforming to IEC 60947-2 1.25 kA at 380 V AC 50/60 Hz conforming to IEC 60947-2 1.25 kA at 400/415 V AC 50/60 Hz conforming to IEC 60947-2
Breaking capacity codeN
Trip unit technologyThermal-magnetic
Trip unit rating40 A at 50 °C
Trip unit nameTM-D
Protection typeShort-circuit protection Overload protection
Earth-leakage protectionWithout
Suitability for isolationYes conforming to IEC 60947-2
Utilisation categoryCategory A
Mechanical durability13000 cycles
Local signallingPositive contact indication
EZC100N1040 — Mechanical
ParameterValue
Connection pitch25 mm
Downside connectionFront
Upside connectionFront
Device short nameEasypact EZC100N
Control typeToggle
Mounting modeFixed
Mounting supportBackplate
Width25 mm
Height130 mm
Depth60 mm
EZC100N1040 — Environmental
ParameterValue
IP degree of protectionIP20 conforming to IEC 60529
IK degree of protectionIK07 conforming to IEC 62262
Pollution degree3 conforming to IEC 60664-1 3 conforming to IEC 947-1
Operating ambient air temperature-25...70 °C
Storage ambient air temperature-35...85 °C
EZC100N1040 — Approvals
ParameterValue
StandardsEN/IEC 60947-1 EN/IEC 60947-2 GB/T 14048.2 JIS C8201-2-2

Product details

The Schneider Electric EZC100N1040 is a 1-pole EasyPact EZC100N circuit breaker rated 40 A at 40 °C, with a thermal-magnetic TM-D trip unit providing short-circuit and overload protection for distribution circuits. It carries a 25 kA Icu breaking capacity at 110-130 V AC (50/60 Hz) per IEC 60947-2, and 18 kA at 220-240 V AC. The 1-pole form factor with a 25 mm width and 60 mm depth fits standard backplate mounting in distribution panels.

At 50 °C the rating holds at 40 A per the TM-D trip curve — no derating needed for moderately warm enclosures. The thermal-magnetic trip responds to sustained overloads (thermal bimetal) and instantaneous short-circuits (magnetic coil), covering the two failure modes a distribution circuit sees. The N breaking capacity code indicates this is the standard-interrupting version of the EZC100N frame. The IP20 finger-safe enclosure protects against solid objects over 12 mm but not against moisture; mount inside a sealed cabinet for wet-area use.

Fixed mounting on a backplate with front-facing connections — both line and load terminate on the front face. The 25 mm pole pitch matches standard DIN-rail terminal block spacing, so it aligns cleanly in a multi-pole distribution row. The toggle actuator gives positive contact indication: you can see and feel the mechanism position. Mechanical durability of 13,000 cycles suits frequent switching applications like lighting contactor replacement or machine tool disconnects. The IK07 impact rating handles accidental tool drops during panel maintenance.

Frequently asked questions

What is the breaking capacity of the EZC100N1040 at different voltages?

The EZC100N1040 has a breaking capacity of 25 kA Icu at 110-130 V AC, 18 kA at 220-240 V AC, 5 kA at 125 V DC (1P), and 2.5 kA at 380-415 V AC, all per IEC 60947-2.

What standards does the EZC100N1040 comply with?

The EZC100N1040 complies with EN/IEC 60947-1, EN/IEC 60947-2, GB/T 14048.2, and JIS C8201-2-2. It is suitable for isolation per IEC 60947-2.

Where can I buy the EZC100N1040 and how is it quoted?

The EZC100N1040 is sourced and quoted to order against an RFQ through independent distribution. Availability and current pricing are confirmed at the time of quote.

MPN