The Schneider Electric EZC100N1045 is a 1-pole EasyPact EZC100N circuit breaker with a thermal-magnetic TM-D trip unit rated 45 A at 50 °C. That 45 A rating governs the continuous load it can carry without tripping on thermal overload — sized for a distribution subfeed or a moderate motor branch circuit. The breaking capacity code N delivers 25 kA Icu at 110–130 V AC and 18 kA at 220–240 V AC, which means it safely interrupts fault currents up to those levels without welding contacts or cascading upstream. At 380–400 V AC the Icu drops to 2.5 kA, so verify the available fault current at the point of installation — this breaker is not a high-SCCR choice for 400 V three-phase panels.
Deployment context
Mounts fixed to a backplate with front-connect wiring — no DIN-rail clip, so plan for panel cutouts and screw-down termination. The 25 mm width per pole keeps the footprint tight in a multi-pole group.