Skip to main content
Schneider Electric EZC100N1080 — Circuit Breaker Accessories

Schneider Electric EZC100N1080 EasyPact EZC100N, 80 A, 1P, 2

MPNEZC100N1080
Active

Schneider Electric EasyPact EZC100N, circuit breaker, EZC100N1080, 80 A, 1P, 25 kA Icu at 110-130 V AC, thermal-magnetic TM-D trip unit.

$39.96Ref. price · indicative, final on quote
StockContact for availability
Lead timeIn Stock wk
MOQ1 pcs
Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Jul 2026
How we verify every order →

Specifications

Identification

EZC100N1080 — Identification
ParameterValue
Product / component typeCircuit breaker
Range of productEasyPact
Device applicationDistribution

Electrical

EZC100N1080 — Electrical
ParameterValue
Network type (AC/DC)DC AC
Rated current [In]80 A at 40 °C
Rated operational voltage [Ue]125 V DC conforming to IEC 60947-2 415 V AC 50/60 Hz conforming to IEC 60947-2
Rated insulation voltage [Ui]690 V AC 50/60 Hz conforming to IEC 60947-2
Rated impulse withstand voltage [Uimp]6 kV conforming to IEC 60947-2
Network frequency50/60 Hz
Poles description1P

Protection & Performance

EZC100N1080 — Protection & Performance
ParameterValue
Breaking capacity25 kA Icu at 110...130 V AC 50/60 Hz conforming to IEC 60947-2 5 kA Icu at 125 V DC 1P conforming to IEC 60947-2 18 kA Icu at 220...240 V AC 50/60 Hz conforming to IEC 60947-2 2.5 kA Icu at 380 V AC 50/60 Hz conforming to IEC 60947-2 2.5 kA Icu at 400...415 V AC 50/60 Hz conforming to IEC 60947-2
Rated service breaking capacity [Ics]12.5 kA at 110/130 V AC 50/60 Hz conforming to IEC 60947-2 2.5 kA at 125 V DC conforming to IEC 60947-2 9 kA at 220/230/240 V AC 50/60 Hz conforming to IEC 60947-2 1.25 kA at 380 V AC 50/60 Hz conforming to IEC 60947-2 1.25 kA at 400/415 V AC 50/60 Hz conforming to IEC 60947-2
Breaking capacity codeN
Trip unit technologyThermal-magnetic
Trip unit rating80 A at 50 °C
Trip unit nameTM-D
Protection typeShort-circuit protection Overload protection
Earth-leakage protectionWithout
Suitability for isolationYes conforming to IEC 60947-2
Utilisation categoryCategory A
Mechanical durability13000 cycles
Local signallingPositive contact indication

Mechanical

EZC100N1080 — Mechanical
ParameterValue
Connection pitch25 mm
Downside connectionFront
Upside connectionFront
Device short nameEasypact EZC100N
Control typeToggle
Mounting modeFixed
Mounting supportBackplate
Width25 mm
Height130 mm
Depth60 mm

Environmental

EZC100N1080 — Environmental
ParameterValue
IP degree of protectionIP20 conforming to IEC 60529
IK degree of protectionIK07 conforming to IEC 62262
Pollution degree3 conforming to IEC 60664-1 3 conforming to IEC 947-1
Operating ambient air temperature-25...70 °C
Storage ambient air temperature-35...85 °C

Approvals

EZC100N1080 — Approvals
ParameterValue
StandardsEN/IEC 60947-1 GB/T 14048.2 EN/IEC 60947-2 JIS C8201-2-2

Product details

Panel fit and protection profile

The Schneider Electric EZC100N1080 is an EasyPact EZC100N circuit breaker — a 1-pole, 80 A thermal-magnetic unit with a TM-D trip curve, sized for distribution panels where a single-phase or DC branch needs short-circuit and overload protection. The 25 mm width per pole keeps the DIN-rail fill factor tight; at 80 A rated current (40 °C ambient, derated to 80 A at 50 °C), it covers feeder and subfeeder duty in a 415 V AC or 125 V DC system. Breaking capacity hits 25 kA Icu at 110-130 V AC, dropping to 18 kA at 220-240 V AC and 2.5 kA at 400-415 V AC — so the upstream fault current available at the panelboard determines which voltage tap you can land it on.

Frequently asked questions

What is the breaking capacity of the EZC100N1080 at 240 V AC?

At 220-240 V AC 50/60 Hz, the EZC100N1080 delivers 18 kA Icu per IEC 60947-2.

What standards does the EZC100N1080 comply with?

The EZC100N1080 is certified to EN/IEC 60947-1, GB/T 14048.2, EN/IEC 60947-2, and JIS C8201-2-2.

MPN