Skip to main content
Schneider Electric EZC100N3100 — Molded Case Circuit Breakers (MCCB)

Schneider Electric EZC100N3100 EasyPact EZC100N 100A 3P MCCB

MPNEZC100N3100
Active

Schneider Electric EasyPact EZC100N series, EZC100N3100, 3-pole MCCB, 100 A thermal-magnetic trip unit (TM-D), 10 kA Icu at 440 V AC, fixed mount, toggle control.

$49.96Ref. price · indicative, final on quote
Source DocumentedChannel stated on listing & quote
Condition PhotosReal unit photos / video on request
WhatsApp AnswersFast human replies for machine-down parts
Worldwide DispatchDHL/FedEx — transit quoted per order
Independent China distributor & sourcing agent· Listing updated Sep 2026

Specifications

EZC100N3100 — Identification
ParameterValue
Product / component typeCircuit breaker
Device applicationDistribution
EZC100N3100 — Mechanical
ParameterValue
Height130 mm
Width75 mm
Depth60 mm
EZC100N3100 — Electrical
ParameterValue
[In] rated current100 A at 40 °C
Breaking capacity10 kA Icu at 440 V AC 50/60 Hz conforming to IEC 60947-2 15 kA Icu at 400...415 V AC 50/60 Hz conforming to IEC 60947-2 18 kA Icu at 380 V AC 50/60 Hz conforming to IEC 60947-2 25 kA Icu at 110...130 V AC 50/60 Hz conforming to IEC 60947-2 25 kA Icu at 220...240 V AC 50/60 Hz conforming to IEC 60947-2 5 kA Icu at 125 V DC 1P conforming to IEC 60947-2 5 kA Icu at 250 V DC 2P conforming to IEC 60947-2 5 kA Icu at 550 V AC 50/60 Hz conforming to IEC 60947-2
[Ics] rated service breaking capacity5 kA at 440 V AC 50/60 Hz conforming to IEC 60947-2 9 kA at 380 V AC 50/60 Hz conforming to IEC 60947-2 12.5 kA at 110/130 V AC 50/60 Hz conforming to IEC 60947-2 12.5 kA at 220/230/240 V AC 50/60 Hz conforming to IEC 60947-2 2.5 kA at 125 V DC conforming to IEC 60947-2 2.5 kA at 250 V DC conforming to IEC 60947-2 2.5 kA at 550 V AC 50/60 Hz conforming to IEC 60947-2 7.5 kA at 400/415 V AC 50/60 Hz conforming to IEC 60947-2
[Ue] rated operational voltage550 V AC 50/60 Hz conforming to IEC 60947-2 250 V DC conforming to IEC 60947-2
[Ui] rated insulation voltage690 V AC 50/60 Hz conforming to IEC 60947-2
EZC100N3100 — Specifications
ParameterValue
Poles description3P
Trip unit nameTM-D
Trip unit technologyThermal-magnetic
Device short nameEasypact EZC100N
StandardsEN/IEC 60947-1 GB/T 14048.2 EN/IEC 60947-2 JIS C8201-2-2

Product details

The Schneider Electric EZC100N3100 is a 3-pole EasyPact EZC100N moulded-case circuit breaker (MCCB) with a thermal-magnetic TM-D trip unit rated 100 A at 50 °C. At 400–415 V the interrupting rating rises to 15 kA Icu, and at 380 V it reaches 18 kA Icu. For DC applications, it interrupts 5 kA Icu at 125 V DC (1-pole) or 250 V DC (2-pole).

This MCCB is a fixed-mount, backplate-supported device with front-front connections (line and load both terminate on the front face). The toggle actuator provides positive contact indication, so you can visually confirm the contact position without removing the cover. IP20 finger protection and IK07 impact resistance suit it for enclosure mounting where incidental contact is possible but washdown or dust ingress is not expected.

Protection and compliance

The EZC100N3100 provides short-circuit and overload protection for distribution circuits. It is Category A (no intentional short-time delay), meaning it trips instantaneously on a fault — suitable for feeder protection where selectivity is achieved upstream. Standards compliance includes EN/IEC 60947-1, EN/IEC 60947-2, GB/T 14048.2, and JIS C8201-2-2.

Frequently asked questions

What is the breaking capacity of EZC100N3100 at 440 V?

The EZC100N3100 has a breaking capacity of 10 kA Icu at 440 V AC 50/60 Hz per IEC 60947-2.

What trip unit does the EZC100N3100 use?

It uses a TM-D thermal-magnetic trip unit rated 100 A at 50 °C.

Where can I buy the EZC100N3100?

The EZC100N3100 is sourced and quoted to order against an RFQ through independent distribution. Availability and current pricing are confirmed at the time of quote.

MPN
EZC100N3100