Skip to main content
Schneider Electric EZC250F3125 — Miniature Circuit Breakers (MCB)

Schneider Electric EZC250F3125 EasyPact EZC250F 125A 3P MCCB

MPNEZC250F3125
Active

Schneider Electric EasyPact EZC250F, 3-pole thermal-magnetic MCCB, 125 A, TM-D trip unit, breaking capacity 10-25 kA per IEC 60947-2, IP20, IK07, fixed mounting.

Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Aug 2026

Specifications

EZC250F3125 — Identification
ParameterValue
Product range (series)EasyPact
Product/component typeCircuit breaker
Device applicationDistribution
EZC250F3125 — Ratings
ParameterValue
Rated current (In)125 A at 40 °C
Poles configuration3P
Breaking capacity10 kA Icu at 440 V AC 50/60 Hz conforming to IEC 60947-2 15 kA Icu at 400...415 V AC 50/60 Hz conforming to IEC 60947-2 18 kA Icu at 380 V AC 50/60 Hz conforming to IEC 60947-2 25 kA Icu at 110...130 V AC 50/60 Hz conforming to IEC 60947-2 25 kA Icu at 220...240 V AC 50/60 Hz conforming to IEC 60947-2 5 kA Icu at 125 V DC 1P conforming to IEC 60947-2 5 kA Icu at 250 V DC 2P conforming to IEC 60947-2 5 kA Icu at 550 V AC 50/60 Hz conforming to IEC 60947-2
Rated service breaking capacity (Ics)9 kA at 380 V AC 50/60 Hz conforming to IEC 60947-2 12.5 kA at 110/130 V AC 50/60 Hz conforming to IEC 60947-2 12.5 kA at 220/230/240 V AC 50/60 Hz conforming to IEC 60947-2 2.5 kA at 125 V DC conforming to IEC 60947-2 2.5 kA at 250 V DC conforming to IEC 60947-2 2.5 kA at 550 V AC 50/60 Hz conforming to IEC 60947-2 9 kA at 400/415 V AC 50/60 Hz conforming to IEC 60947-2 7.5 kA at 440 V AC 50/60 Hz conforming to IEC 60947-2
Rated operational voltage (Ue)550 V AC 50/60 Hz conforming to IEC 60947-2 250 V DC conforming to IEC 60947-2
Rated insulation voltage (Ui)690 V AC 50/60 Hz conforming to IEC 60947-2
Rated impulse withstand voltage (Uimp)6 kV conforming to IEC 60947-2
Network type (AC/DC)DC AC
Network frequency50/60 Hz
Utilisation categoryCategory A
EZC250F3125 — Protection
ParameterValue
Trip unit technologyThermal-magnetic
Earth-leakage protectionWithout
Suitability for isolationYes conforming to IEC 60947-2
Mechanical durability (cycles)10000 cycles
EZC250F3125 — Mechanical
ParameterValue
Mounting supportBackplate
Mounting modeFixed
Control typeToggle
Local signalling/indicationPositive contact indication
Width105 mm
Height165 mm
Depth60 mm
EZC250F3125 — Environmental
ParameterValue
Operating ambient temperature-25...70 °C
Storage ambient temperature-35...85 °C
IP degree of protectionIP20 conforming to IEC 60529
Pollution degree3 conforming to IEC 60664-1 3 conforming to IEC 947-1
EZC250F3125 — Approvals
ParameterValue
StandardsEN/IEC 60947-2 GB/T 14048.2 EN/IEC 60947-1

Product details

Schneider Electric EZC250F3125 is a 3-pole EasyPact EZC250F thermal-magnetic moulded-case circuit breaker (MCCB). Breaking capacity hits 10 kA Icu at 440 V AC, 15 kA at 400-415 V, 18 kA at 380 V, and 25 kA at 220-240 V — all per IEC 60947-2. For DC circuits: 5 kA Icu at 250 V DC 2P. It's Category A (no intentional short-time delay), so it's a standard distribution breaker, not a selective main.

That TM-D thermal-magnetic trip curve means the thermal element handles sustained overloads (cable protection), and the magnetic element snaps on short-circuit. At 380 V that rises to 18 kA, at 220-240 V to 25 kA. Pick your system voltage, that's your interrupting rating. The 690 V rated insulation voltage (Ui) and 550 V rated operational voltage (Ue) frame the system voltage ceiling. It's rated for isolation per IEC 60947-2, so you can use it as a visible-break disconnect.

Fixed mounting on a backplate with front-connect terminals — both line and load connections are front-accessed. Connection pitch is 35 mm per pole. Dimensions: 105 mm wide, 165 mm tall, 60 mm deep. IP20 finger-safe enclosure, IK07 impact resistance. Toggle control with positive contact indication — you can see the contact state through the window. No earth-leakage module on this variant; it's a straight thermal-magnetic breaker.

Frequently asked questions

What is the breaking capacity of the EZC250F3125 at 440 V?

10 kA Icu at 440 V AC 50/60 Hz per IEC 60947-2. At 400-415 V it's 15 kA; at 380 V it's 18 kA; at 220-240 V it's 25 kA. For DC: 5 kA at 250 V DC 2P.

What standards does the EZC250F3125 comply with?

EN/IEC 60947-2 and GB/T 14048.2. Also conforms to IEC 60664-1 for pollution degree 3 and IEC 62262 for IK07 impact rating.

Where can I buy the EZC250F3125 and how is it quoted?

Sourced through independent distribution channels. Quoted to order against an RFQ — availability and current pricing are confirmed at quote time. No stock or price figures on this page.

MPN
EZC250F3125