Skip to main content
Schneider Electric EZC250F3150 — Circuit Breaker Accessories

Schneider Electric EZC250F3150 EasyPact EZC250F, 150 A, 3P,

MPNEZC250F3150
Active

Schneider Electric EasyPact EZC250F series, EZC250F3150, 3-pole molded case circuit breaker, 150 A rated current, thermal-magnetic TM-D trip unit, 10 kA Icu at 440 V AC, IP20.

Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Aug 2026

Specifications

EZC250F3150 — Identification
ParameterValue
Product / component typeCircuit breaker
Range of productEasyPact
Device applicationDistribution
EZC250F3150 — Electrical
ParameterValue
Network type (AC/DC)AC DC
Rated current [In]150 A at 40 °C
Rated operational voltage [Ue]550 V AC 50/60 Hz conforming to IEC 60947-2 250 V DC conforming to IEC 60947-2
Rated insulation voltage [Ui]690 V AC 50/60 Hz conforming to IEC 60947-2
Rated impulse withstand voltage [Uimp]6 kV conforming to IEC 60947-2
Network frequency50/60 Hz
Poles description3P
EZC250F3150 — Protection & Performance
ParameterValue
Breaking capacity10 kA Icu at 440 V AC 50/60 Hz conforming to IEC 60947-2 15 kA Icu at 400...415 V AC 50/60 Hz conforming to IEC 60947-2 18 kA Icu at 380 V AC 50/60 Hz conforming to IEC 60947-2 25 kA Icu at 110...130 V AC 50/60 Hz conforming to IEC 60947-2 25 kA Icu at 220...240 V AC 50/60 Hz conforming to IEC 60947-2 5 kA Icu at 125 V DC 1P conforming to IEC 60947-2 5 kA Icu at 250 V DC 2P conforming to IEC 60947-2 5 kA Icu at 550 V AC 50/60 Hz conforming to IEC 60947-2
Rated service breaking capacity [Ics]9 kA at 380 V AC 50/60 Hz conforming to IEC 60947-2 12.5 kA at 110/130 V AC 50/60 Hz conforming to IEC 60947-2 12.5 kA at 220/230/240 V AC 50/60 Hz conforming to IEC 60947-2 2.5 kA at 125 V DC conforming to IEC 60947-2 2.5 kA at 250 V DC conforming to IEC 60947-2 2.5 kA at 550 V AC 50/60 Hz conforming to IEC 60947-2 9 kA at 400/415 V AC 50/60 Hz conforming to IEC 60947-2 7.5 kA at 440 V AC 50/60 Hz conforming to IEC 60947-2
Breaking capacity codeF
Trip unit technologyThermal-magnetic
Trip unit rating150 A at 50 °C
Trip unit nameTM-D
Protection typeOverload protection Short-circuit protection
Earth-leakage protectionWithout
Suitability for isolationYes conforming to IEC 60947-2
Utilisation categoryCategory A
Mechanical durability10000 cycles
Local signallingPositive contact indication
EZC250F3150 — Mechanical
ParameterValue
Connection pitch35 mm
Downside connectionFront
Upside connectionFront
Device short nameEasypact EZC250F
Control typeToggle
Mounting modeFixed
Mounting supportBackplate
Width105 mm
Height165 mm
Depth60 mm
EZC250F3150 — Environmental
ParameterValue
IP degree of protectionIP20 conforming to IEC 60529
IK degree of protectionIK07 conforming to IEC 62262
Pollution degree3 conforming to IEC 60664-1 3 conforming to IEC 947-1
Operating ambient air temperature-25...70 °C
Storage ambient air temperature-35...85 °C
EZC250F3150 — Approvals
ParameterValue
StandardsGB/T 14048.2 EN/IEC 60947-2 EN/IEC 60947-1

Product details

The Schneider Electric EZC250F3150 is a 3-pole molded case circuit breaker from the EasyPact EZC250F range, rated 150 A at 40 °C with a thermal-magnetic TM-D trip unit. It's built for distribution duty in fixed-mount backplate panels — the 105 mm wide, 165 mm high, 60 mm deep footprint fits standard enclosure cutouts. The 10 kA Icu at 440 V AC (18 kA at 380 V, 25 kA at 240 V) covers most commercial and light industrial service-entrance and feeder applications where fault levels stay under that ceiling. Category A utilization means it's not intended for motor starting — this is a distribution breaker, not a motor circuit protector.

Breaking capacity across voltage — the real-world read

The interrupting rating climbs as system voltage drops: 25 kA Icu at 240 V AC, 18 kA at 380 V, 15 kA at 400–415 V, and 10 kA at 440 V. The DC side is more modest: 5 kA Icu at 125 V DC (1-pole) or 250 V DC (2-pole). The 690 V insulation voltage (Ui) gives headroom for 480/277 V systems common in North American commercial panels.

Fixed-mount on a backplate — no DIN-rail adapter on this frame. The toggle handle provides positive contact indication (ON/OFF visible on the front face). IP20 finger-safe protection on the front; IK07 impact resistance covers incidental tool drops.

Frequently asked questions

What is the breaking capacity of EZC250F3150 at 440 V AC?

10 kA Icu at 440 V AC 50/60 Hz per IEC 60947-2. At 400–415 V it's 15 kA, and at 380 V it's 18 kA. The DC rating is 5 kA at 125 V DC (1-pole) or 250 V DC (2-pole).

Where can I buy EZC250F3150 and how do I get a price?

This part is sourced to order against an RFQ through independent industrial distribution channels. Submit an RFQ for current availability and pricing — confirmed at quote time, not from a static listing.

What compliance documentation does this breaker carry?

Certified to EN/IEC 60947-2 (circuit-breaker standard) and GB/T 14048.2 (China national standard). Suitable for isolation per IEC 60947-2. IP20 front protection, IK07 impact rating, and Pollution Degree 3 per IEC 60664-1.

MPN