Skip to main content
Schneider Electric EZC250F3200 — Circuit Breaker Accessories

Schneider Electric EZC250F3200 EasyPact EZC250F Circuit Brea

MPNEZC250F3200
Active

Schneider Electric EasyPact EZC250F series, EZC250F3200, 3-pole molded case circuit breaker, 200 A rated current, thermal-magnetic TM-D trip unit, 25 kA Icu at 240 V AC.

$123.13Ref. price · indicative, final on quote
Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Aug 2026

Specifications

EZC250F3200 — Identification
ParameterValue
Product / component typeCircuit breaker
Range of productEasyPact
Device applicationDistribution
EZC250F3200 — Electrical
ParameterValue
Network type (AC/DC)AC DC
Rated current [In]200 A at 40 °C
Rated operational voltage [Ue]550 V AC 50/60 Hz conforming to IEC 60947-2 250 V DC conforming to IEC 60947-2
Rated insulation voltage [Ui]690 V AC 50/60 Hz conforming to IEC 60947-2
Rated impulse withstand voltage [Uimp]6 kV conforming to IEC 60947-2
Network frequency50/60 Hz
Poles description3P
EZC250F3200 — Protection & Performance
ParameterValue
Breaking capacity10 kA Icu at 440 V AC 50/60 Hz conforming to IEC 60947-2 15 kA Icu at 400...415 V AC 50/60 Hz conforming to IEC 60947-2 18 kA Icu at 380 V AC 50/60 Hz conforming to IEC 60947-2 25 kA Icu at 110...130 V AC 50/60 Hz conforming to IEC 60947-2 25 kA Icu at 220...240 V AC 50/60 Hz conforming to IEC 60947-2 5 kA Icu at 125 V DC 1P conforming to IEC 60947-2 5 kA Icu at 250 V DC 2P conforming to IEC 60947-2 5 kA Icu at 550 V AC 50/60 Hz conforming to IEC 60947-2
Rated service breaking capacity [Ics]9 kA at 380 V AC 50/60 Hz conforming to IEC 60947-2 12.5 kA at 110/130 V AC 50/60 Hz conforming to IEC 60947-2 12.5 kA at 220/230/240 V AC 50/60 Hz conforming to IEC 60947-2 2.5 kA at 125 V DC conforming to IEC 60947-2 2.5 kA at 250 V DC conforming to IEC 60947-2 2.5 kA at 550 V AC 50/60 Hz conforming to IEC 60947-2 9 kA at 400/415 V AC 50/60 Hz conforming to IEC 60947-2 7.5 kA at 440 V AC 50/60 Hz conforming to IEC 60947-2
Breaking capacity codeF
Trip unit technologyThermal-magnetic
Trip unit rating200 A at 50 °C
Trip unit nameTM-D
Protection typeShort-circuit protection Overload protection
Earth-leakage protectionWithout
Suitability for isolationYes conforming to IEC 60947-2
Utilisation categoryCategory A
Mechanical durability10000 cycles
Local signallingPositive contact indication
EZC250F3200 — Mechanical
ParameterValue
Connection pitch35 mm
Downside connectionFront
Upside connectionFront
Device short nameEasypact EZC250F
Control typeToggle
Mounting modeFixed
Mounting supportBackplate
Width105 mm
Height165 mm
Depth60 mm
EZC250F3200 — Environmental
ParameterValue
IP degree of protectionIP20 conforming to IEC 60529
IK degree of protectionIK07 conforming to IEC 62262
Pollution degree3 conforming to IEC 60664-1 3 conforming to IEC 947-1
Operating ambient air temperature-25...70 °C
Storage ambient air temperature-35...85 °C
EZC250F3200 — Approvals
ParameterValue
StandardsJIS C8201-2-2 EN/IEC 60947-2 GB/T 14048.2 EN/IEC 60947-1

Product details

Breaking capacity varies with voltage: 25 kA Icu at 220–240 V AC, 18 kA at 380 V AC, 15 kA at 400–415 V AC, and 10 kA at 440 V AC. For DC applications, it delivers 5 kA Icu at 125 V DC (1P) or 250 V DC (2P).

The 105 mm width and 165 mm height fit standard backplate layouts; depth is 60 mm. IP20 finger-safe protection on the front face, IK07 impact resistance.

Frequently asked questions

What is the breaking capacity of EZC250F3200 at 240 V AC?

25 kA Icu at 220–240 V AC, conforming to IEC 60947-2.

Where can I buy EZC250F3200 and get a price?

This part is sourced to order against an RFQ through independent distribution. Submit an RFQ for availability and current pricing.

What standards does EZC250F3200 comply with?

It complies with JIS C8201-2-2, EN/IEC 60947-2, GB/T 14048.2, and EN/IEC 60947-1.

MPN