The Schneider Electric EZC250N3160 is an EasyPact EZC250N 3-pole circuit breaker with a thermal-magnetic TM-D trip unit, rated 160 A at 40 °C and 160 A at 50 °C. For lower voltages the interrupting rating climbs: 50 kA at 220–240 V AC and 25 kA at 380–415 V AC, which gives you headroom on common industrial distribution voltages.
Fixed backplate mount with front-facing connections on both line and load sides — the 35 mm connection pitch matches standard busbar systems and DIN-rail terminal blocks. At 105 mm wide, 165 mm tall, and 60 mm deep, it fits a standard distribution enclosure without crowding adjacent breakers. IP20 finger-safe protection on the front face; the IK07 impact rating means it withstands accidental tool strikes during panel work.
Certified to GB/T 14048.2, EN/IEC 60947-1, and EN/IEC 60947-2 — the core standards for low-voltage switchgear and controlgear. Category A utilisation means it is not intended for frequent motor switching — it is a distribution breaker, not a motor-starter combination.