Skip to main content
Schneider Electric EZC250N3160 — Circuit Breaker Accessories

Schneider Electric EZC250N3160 EasyPact EZC250N Circuit Brea

MPNEZC250N3160
Active

Schneider Electric EasyPact EZC250N, EZC250N3160, 3-pole circuit breaker, 160 A rated, 20 kA Icu at 440 V AC, thermal-magnetic TM-D trip unit, fixed mount, IP20.

$134.18Ref. price · indicative, final on quote
Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Aug 2026

Specifications

EZC250N3160 — Identification
ParameterValue
Product / component typeCircuit breaker
Range of productEasyPact
Device applicationDistribution
EZC250N3160 — Electrical
ParameterValue
Network type (AC/DC)DC AC
Rated current [In]160 A at 40 °C
Rated operational voltage [Ue]550 V AC 50/60 Hz conforming to IEC 60947-2 250 V DC conforming to IEC 60947-2
Rated insulation voltage [Ui]690 V AC 50/60 Hz conforming to IEC 60947-2
Rated impulse withstand voltage [Uimp]6 kV conforming to IEC 60947-2
Network frequency50/60 Hz
Poles description3P
EZC250N3160 — Protection & Performance
ParameterValue
Breaking capacity20 kA Icu at 440 V AC 50/60 Hz conforming to IEC 60947-2 50 kA Icu at 110...130 V AC 50/60 Hz conforming to IEC 60947-2 50 kA Icu at 220...240 V AC 50/60 Hz conforming to IEC 60947-2 20 kA Icu at 125 V DC 1P conforming to IEC 60947-2 20 kA Icu at 250 V DC 2P conforming to IEC 60947-2 25 kA Icu at 380 V AC 50/60 Hz conforming to IEC 60947-2 25 kA Icu at 400...415 V AC 50/60 Hz conforming to IEC 60947-2 8 kA Icu at 550 V AC 50/60 Hz conforming to IEC 60947-2
Rated service breaking capacity [Ics]10 kA at 440 V AC 50/60 Hz conforming to IEC 60947-2 25 kA at 110/130 V AC 50/60 Hz conforming to IEC 60947-2 10 kA at 125 V DC conforming to IEC 60947-2 10 kA at 250 V DC conforming to IEC 60947-2 25 kA at 220/230/240 V AC 50/60 Hz conforming to IEC 60947-2 4 kA at 550 V AC 50/60 Hz conforming to IEC 60947-2 12.5 kA at 380 V AC 50/60 Hz conforming to IEC 60947-2 12.5 kA at 400/415 V AC 50/60 Hz conforming to IEC 60947-2
Breaking capacity codeN
Trip unit technologyThermal-magnetic
Trip unit rating160 A at 50 °C
Trip unit nameTM-D
Protection typeOverload protection Short-circuit protection
Earth-leakage protectionWithout
Suitability for isolationYes conforming to IEC 60947-2
Utilisation categoryCategory A
Mechanical durability10000 cycles
Local signallingPositive contact indication
EZC250N3160 — Mechanical
ParameterValue
Connection pitch35 mm
Downside connectionFront
Upside connectionFront
Device short nameEasypact EZC250N
Control typeToggle
Mounting modeFixed
Mounting supportBackplate
Width105 mm
Height165 mm
Depth60 mm
EZC250N3160 — Environmental
ParameterValue
IP degree of protectionIP20 conforming to IEC 60529
IK degree of protectionIK07 conforming to IEC 62262
Pollution degree3 conforming to IEC 60664-1 3 conforming to IEC 947-1
Operating ambient air temperature-25...70 °C
Storage ambient air temperature-35...85 °C
EZC250N3160 — Approvals
ParameterValue
StandardsGB/T 14048.2 EN/IEC 60947-1 EN/IEC 60947-2

Product details

The Schneider Electric EZC250N3160 is an EasyPact EZC250N 3-pole circuit breaker with a thermal-magnetic TM-D trip unit, rated 160 A at 40 °C and 160 A at 50 °C. For lower voltages the interrupting rating climbs: 50 kA at 220–240 V AC and 25 kA at 380–415 V AC, which gives you headroom on common industrial distribution voltages.

Fixed backplate mount with front-facing connections on both line and load sides — the 35 mm connection pitch matches standard busbar systems and DIN-rail terminal blocks. At 105 mm wide, 165 mm tall, and 60 mm deep, it fits a standard distribution enclosure without crowding adjacent breakers. IP20 finger-safe protection on the front face; the IK07 impact rating means it withstands accidental tool strikes during panel work.

Certified to GB/T 14048.2, EN/IEC 60947-1, and EN/IEC 60947-2 — the core standards for low-voltage switchgear and controlgear. Category A utilisation means it is not intended for frequent motor switching — it is a distribution breaker, not a motor-starter combination.

Frequently asked questions

What is the breaking capacity of the EZC250N3160 at 440 V AC?

20 kA Icu at 440 V AC 50/60 Hz per IEC 60947-2. At 380–415 V AC it rises to 25 kA, and at 220–240 V AC it reaches 50 kA.

Where can I buy the EZC250N3160?

Sourced and quoted to order against an RFQ through independent distribution channels. Availability and current pricing are confirmed at quote time.

What compliance standards does the EZC250N3160 meet?

Certified to GB/T 14048.2, EN/IEC 60947-1, and EN/IEC 60947-2. Rated for pollution degree 3 and isolation suitability per IEC 60947-2.

MPN