Skip to main content
Schneider Electric EZC250N4100 — Circuit Breaker Accessories

Schneider Electric EZC250N4100 EasyPact EZC250N Circuit Brea

MPNEZC250N4100
Active

Schneider Electric EasyPact EZC250N, circuit breaker, 4P, 100 A, TM-D trip unit, 20 kA Icu at 440 V AC, front connections, fixed mount.

$130.83Ref. price · indicative, final on quote
Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Aug 2026

Specifications

EZC250N4100 — Identification
ParameterValue
Product / component typeCircuit breaker
Range of productEasyPact
Device applicationDistribution
EZC250N4100 — Electrical
ParameterValue
Network type (AC/DC)DC AC
Rated current [In]100 A at 40 °C
Rated operational voltage [Ue]550 V AC 50/60 Hz conforming to IEC 60947-2 250 V DC conforming to IEC 60947-2
Rated insulation voltage [Ui]690 V AC 50/60 Hz conforming to IEC 60947-2
Rated impulse withstand voltage [Uimp]6 kV conforming to IEC 60947-2
Network frequency50/60 Hz
Poles description4P
EZC250N4100 — Protection & Performance
ParameterValue
Breaking capacity20 kA Icu at 440 V AC 50/60 Hz conforming to IEC 60947-2 50 kA Icu at 220...240 V AC 50/60 Hz conforming to IEC 60947-2 20 kA Icu at 125 V DC 1P conforming to IEC 60947-2 20 kA Icu at 250 V DC 2P conforming to IEC 60947-2 8 kA Icu at 550 V AC 50/60 Hz conforming to IEC 60947-2 25 kA Icu at 380...415 V AC 50/60 Hz conforming to IEC 60947-2
Rated service breaking capacity [Ics]10 kA at 440 V AC 50/60 Hz conforming to IEC 60947-2 25 kA at 220...240 V AC 50/60 Hz conforming to IEC 60947-2 10 kA at 125 V DC conforming to IEC 60947-2 10 kA at 250 V DC conforming to IEC 60947-2 4 kA at 550 V AC 50/60 Hz conforming to IEC 60947-2 12.5 kA at 380...415 V AC 50/60 Hz conforming to IEC 60947-2
Breaking capacity codeN
Trip unit technologyThermal-magnetic
Trip unit rating100 A at 50 °C
Trip unit nameTM-D
Protection typeOverload protection Short-circuit protection
Earth-leakage protectionWithout
Suitability for isolationYes conforming to IEC 60947-2
Utilisation categoryCategory A
Mechanical durability10000 cycles
Local signallingPositive contact indication
EZC250N4100 — Mechanical
ParameterValue
Connection pitch35 mm
Downside connectionFront
Upside connectionFront
Device short nameEasypact EZC250N
Control typeToggle
Mounting modeFixed
Mounting supportBackplate
Width140 mm
Height165 mm
Depth60 mm
EZC250N4100 — Environmental
ParameterValue
IP degree of protectionIP20 conforming to IEC 60529
IK degree of protectionIK07 conforming to EN 50102
Pollution degree3 conforming to IEC 60947
Operating ambient air temperature-25...70 °C
Storage ambient air temperature-35...85 °C
EZC250N4100 — Approvals
ParameterValue
StandardsJIS C8201-2-2 GB/T 14048.2 EN/IEC 60947-1 EN/IEC 60947-2

Product details

The Schneider Electric EZC250N4100 is a 4-pole EasyPact EZC250N circuit breaker with a fixed thermal-magnetic TM-D trip unit rated 100 A at 40 °C (100 A at 50 °C). The N breaking capacity code means it delivers 20 kA Icu at 440 V AC 50/60 Hz, with higher ratings at lower voltages: 50 kA Icu at 220...240 V AC and 25 kA Icu at 380...415 V AC. For DC circuits, it offers 20 kA Icu at 125 V DC (1P) and 20 kA Icu at 250 V DC (2P). This makes it suitable for main or branch feeder protection where fault levels are moderate.

Mounts fixed to a backplate via the 35 mm connection pitch. Front-facing connections on both line and load sides simplify busbar or cable routing in a panel. The toggle handle provides positive contact indication — you can see the contact state without removing the cover. IP20 finger-safe protection on the front, IK07 impact resistance. Pollution degree 3 per IEC 60947 means it tolerates conductive pollution in industrial environments.

Frequently asked questions

Where can I buy EZC250N4100 and how do I get a price?

The EZC250N4100 is sourced and quoted to order against an RFQ through independent distribution. Submit an RFQ for current pricing and availability.

What is EZC250N4100's breaking capacity at 440 V AC?

20 kA Icu at 440 V AC 50/60 Hz per IEC 60947-2. At 380...415 V AC it rises to 25 kA Icu.

What compliance documentation does this brand provide for EZC250N4100?

The breaker is certified to JIS C8201-2-2, GB/T 14048.2, EN/IEC 60947-1, and EN/IEC 60947-2. It carries IP20 per IEC 60529 and IK07 per EN 50102.

MPN