Schneider Electric EZC250N44160

Schneider EasyPact EZC250N44160 160A MCCB, 20kA at 440V AC

MPN EZC250N44160
Obsolete

Schneider Electric EasyPact EZC250N, MCCB, 4P, 160 A (40 °C), TM-D trip unit, 20 kA Icu at 440 V AC, fixed mount, toggle control.

Dispatch SLA24-48h Global Rush
Quality CheckOriginal Seal & Physical QC
IncotermsDAP / DDP Available
Source DocumentedChannel stated on listing & quote
Condition PhotosReal unit photos / video on request
WhatsApp AnswersFast human replies for machine-down parts
Worldwide DispatchDHL/FedEx — transit quoted per order
Independent China distributor & stockist· Listing updated Sep 2026

Specifications

EZC250N44160 key specifications
ParameterValue
Control typeToggle
Trip unit typeThermal-magnetic
Main product or component typeCircuit breaker
Voltage550 V AC 50/60 Hz conforming to IEC 60947-2 250 V DC conforming to IEC 60947-2
Insulation voltage ui690 V AC 50/60 Hz conforming to IEC 60947-2
Breaking capacity20 kA Icu at 440 V AC 50/60 Hz conforming to IEC 60947-2 50 kA Icu at 220...240 V AC 50/60 Hz conforming to IEC 60947-2 20 kA Icu at 125 V DC 1P conforming to IEC 60947-2 20 kA Icu at 250 V DC 2P conforming to IEC 60947-2 8 kA Icu at 550 V AC 50/60 Hz conforming to IEC 60947-2 25 kA Icu at 380...415 V AC 50/60 Hz conforming to IEC 60947-2
IP ratingIP20
Terminal pitch35 mm
Connection surface topFront
Connection surface bottomFront
Temp storage max85 °C
Temp storage min-35 °C

All specifications

EZC250N44160 additional specifications
ParameterValue
Temp operating max70 °C
Temp operating min-25 °C
Storage temperature-35...85 °C
Pollution degree3 conforming to IEC 60947
Depth60 mm
Width140 mm
Height165 mm
Mechanical life cycles10000 cycles
ApplicationDistribution
Operating temperature-25...70 °C

Product details

MCCB for distribution panels — 160 A, 4-pole, thermal-magnetic

The Schneider Electric EasyPact EZC250N44160 is a 4-pole MCCB rated 160 A at 40 °C (trip unit TM-D, 160 A at 50 °C) for distribution duty in commercial and industrial panels. Its 20 kA Icu at 440 V AC (IEC 60947-2) covers most building and light industrial fault levels; the same breaker delivers 50 kA Icu at 240 V AC and 25 kA at 380–415 V AC. The thermal-magnetic trip handles overload and short-circuit protection — no earth-leakage module on this variant. Pollution degree 3 and IP20 enclosure make it a standard fit for enclosed switchboards.

The N breaking-capacity code (20 kA Icu at 440 V AC) is the mid-range option in the EZC250 family. For the same frame size, the H code steps up to 36 kA Icu at 440 V AC — worth considering if the fault level at the panel exceeds 20 kA. At 380–415 V AC this breaker holds 25 kA Icu, so it coordinates with most upstream 25 kA or 36 kA molded-case breakers in a standard distribution hierarchy.

Fixed mount on a backplate (screw-mount, not DIN rail). Dimensions 165 mm high × 140 mm wide × 60 mm deep. Connection pitch 35 mm. Toggle handle with positive contact indication — no rotary handle on this variant. IP20 finger-safe terminals; IK07 impact rating for the enclosure.

MPN
EZC250N44160