Schneider Electric EZC400N44320 — Circuit Breaker Accessories

Schneider Electric EZC400N44320 EasyPact EZC400N Circuit Bre

MPNEZC400N44320
Obsolete

Schneider Electric EasyPact EZC400N, 4-pole circuit breaker, 400 A rated current at 40 °C, 36 kA Icu at 440 V AC, thermal-magnetic TM-D trip unit, fixed mount, IP20.

Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Jul 2026

Specifications

EZC400N44320 — Identification
ParameterValue
Product / component typeCircuit breaker
Range of productEasyPact
Device applicationDistribution
EZC400N44320 — Electrical
ParameterValue
Network type (AC/DC)AC
Rated current [In]400 A at 40 °C
Rated operational voltage [Ue]440 V AC 50/60 Hz conforming to IEC 60947-2
Rated insulation voltage [Ui]690 V AC 50/60 Hz conforming to IEC 60947-2
Rated impulse withstand voltage [Uimp]8 kV conforming to IEC 60947-2
Network frequency50/60 Hz
Poles description4P
EZC400N44320 — Protection & Performance
ParameterValue
Breaking capacity36 kA Icu at 440 V AC 50/60 Hz conforming to IEC 60947-2 40 kA Icu at 220/230 V AC 50/60 Hz conforming to IEC 60947-2 36 kA Icu at 380 V AC 50/60 Hz conforming to IEC 60947-2 36 kA Icu at 400/415 V AC 50/60 Hz conforming to IEC 60947-2
Rated service breaking capacity [Ics]18 kA at 440 V AC 50/60 Hz conforming to IEC 60947-2 20 kA at 220/230 V AC 50/60 Hz conforming to IEC 60947-2 18 kA at 380 V AC 50/60 Hz conforming to IEC 60947-2 18 kA at 400/415 V AC 50/60 Hz conforming to IEC 60947-2
Breaking capacity codeN
Trip unit technologyThermal-magnetic
Trip unit rating320 A at 50 °C
Trip unit nameTM-D
Protection typeShort-circuit protection Overload protection
Earth-leakage protectionWithout
Suitability for isolationYes conforming to IEC 60947-2
Utilisation categoryCategory A
Mechanical durability10000 cycles
Electrical durabilityCategory A: 4000 cycles 415 V AC 50/60 Hz conforming to IEC 60947-2
Local signallingPositive contact indication
Contact position indicatorYes
EZC400N44320 — Mechanical
ParameterValue
Connection pitch44 mm
Downside connectionFront
Upside connectionFront
Device short nameEasypact EZC400N
Control typeToggle
Mounting modeFixed
Mounting supportBackplate
Width185 mm
Height255 mm
Depth140 mm
ColourBlack
EZC400N44320 — Environmental
ParameterValue
IP degree of protectionIP20 conforming to IEC 60529
IK degree of protectionIK07 conforming to EN 50102
Pollution degree3 conforming to IEC 60947
Operating ambient air temperature-25...70 °C
Storage ambient air temperature-35...85 °C
EZC400N44320 — Approvals
ParameterValue
StandardsEN/IEC 60947-2 EN/IEC 60947-1 JIS C8201-2-2 GB/T 14048.2

Product details

The EZC400N44320 is a 4-pole EasyPact EZC400N circuit breaker rated 400 A at 40 °C with a TM-D thermal-magnetic trip unit. The magnetic trip is fixed at 4000 A, so it clears short-circuits fast; the thermal element handles overloads.

Where it goes in the panel

Fixed-mount on a backplate, front-connected both line and load sides. The 44 mm connection pitch matches standard busbar spacing for 4-pole breakers. IP20 means finger-safe but not washdown — keep it inside a closed enclosure. IK07 gives basic impact resistance for panel handling. The toggle control provides positive contact indication so you can visually confirm the contact position without removing the cover.

Designed to EN/IEC 60947-2, EN/IEC 60947-1, JIS C8201-2-2, and GB/T 14048.2. Suitable for isolation per IEC 60947-2. Pollution degree 3 — rated for industrial environments where conductive pollution may occur. No earth-leakage protection; the TM-D trip covers short-circuit and overload only.

Frequently asked questions

What is the breaking capacity of EZC400N44320?

36 kA Icu at 440 V AC 50/60 Hz per IEC 60947-2. Also rated 40 kA at 220/230 V AC and 36 kA at 380 V and 400/415 V AC.

Where can I buy EZC400N44320?

Sourced and quoted to order against an RFQ through independent distribution. Availability and current pricing confirmed at quote time.

MPN