Schneider Electric EZC400N44400 — Circuit Breaker Accessories

Schneider Electric EZC400N44400 EasyPact EZC400N 400A 4P Cir

MPNEZC400N44400
Obsolete

Schneider Electric EasyPact EZC400N, 400 A, 4-pole, thermal-magnetic circuit breaker, 36 kA Icu at 440 V AC, fixed mount, front connection, black.

Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Jul 2026

Specifications

EZC400N44400 — Identification
ParameterValue
Product / component typeCircuit breaker
Range of productEasyPact
Device applicationDistribution
EZC400N44400 — Electrical
ParameterValue
Network type (AC/DC)AC
Rated current [In]400 A at 40 °C
Rated operational voltage [Ue]440 V AC 50/60 Hz conforming to IEC 60947-2
Rated insulation voltage [Ui]690 V AC 50/60 Hz conforming to IEC 60947-2
Rated impulse withstand voltage [Uimp]8 kV conforming to IEC 60947-2
Network frequency50/60 Hz
Poles description4P
EZC400N44400 — Protection & Performance
ParameterValue
Breaking capacity36 kA Icu at 440 V AC 50/60 Hz conforming to IEC 60947-2 40 kA Icu at 220/230 V AC 50/60 Hz conforming to IEC 60947-2 36 kA Icu at 380 V AC 50/60 Hz conforming to IEC 60947-2 36 kA Icu at 400/415 V AC 50/60 Hz conforming to IEC 60947-2
Rated service breaking capacity [Ics]18 kA at 440 V AC 50/60 Hz conforming to IEC 60947-2 20 kA at 220/230 V AC 50/60 Hz conforming to IEC 60947-2 18 kA at 380 V AC 50/60 Hz conforming to IEC 60947-2 18 kA at 400/415 V AC 50/60 Hz conforming to IEC 60947-2
Breaking capacity codeN
Trip unit technologyThermal-magnetic
Trip unit rating400 A at 50 °C
Trip unit nameTM-D
Protection typeShort-circuit protection Overload protection
Earth-leakage protectionWithout
Suitability for isolationYes conforming to IEC 60947-2
Utilisation categoryCategory A
Mechanical durability10000 cycles
Electrical durabilityCategory A: 4000 cycles 415 V AC 50/60 Hz conforming to IEC 60947-2
Local signallingPositive contact indication
Contact position indicatorYes
EZC400N44400 — Mechanical
ParameterValue
Connection pitch45 mm
Downside connectionFront
Upside connectionFront
Device short nameEasypact EZC400N
Control typeToggle
Mounting modeFixed
Mounting supportBackplate
Width185 mm
Height255 mm
Depth140 mm
ColourBlack
EZC400N44400 — Environmental
ParameterValue
IP degree of protectionIP20 conforming to IEC 60529
IK degree of protectionIK07 conforming to EN 50102
Pollution degree3 conforming to IEC 60947
Operating ambient air temperature-25...70 °C
Storage ambient air temperature-35...85 °C
EZC400N44400 — Approvals
ParameterValue
StandardsEN/IEC 60947-2 EN/IEC 60947-1 JIS C8201-2-2 GB/T 14048.2

Product details

It's a distribution-class breaker (Category A per IEC 60947-2) rated for 36 kA Icu at 440 V AC, 50/60 Hz — enough fault-interrupting capacity for most low-voltage distribution panels feeding motor control centers or lighting sub-distribution. The TM-D trip unit provides short-circuit and overload protection, with a fixed magnetic trip threshold of 6000 A. No earth-leakage protection built in — that's a separate add-on if the application needs it.

Fixed backplate mount, front-front connections (line and load both front-facing). Connection pitch is 45 mm. Dimensions: 255 mm high, 185 mm wide, 140 mm deep. IP20 finger-safe protection on the front; IK07 impact resistance. The toggle handle gives positive contact indication — you can see and feel the open/closed state. Mechanical durability is 10,000 cycles; electrical durability is 4,000 cycles at 415 V AC (Category A). That's enough for a main breaker that gets cycled a few times a year, but not for a switching duty on a frequent-start load.

Listed to EN/IEC 60947-2, EN/IEC 60947-1, JIS C8201-2-2, and GB/T 14048.2. That covers most global markets — Europe, Japan, China.

Frequently asked questions

Where can I buy the EZC400N44400 and get a price?

This part is sourced to order against an RFQ through independent distribution. Submit a request for quote; availability and current pricing are confirmed at quote time.

What is the breaking capacity of the EZC400N44400?

The breaking capacity is 36 kA Icu at 440 V AC, 40 kA Icu at 220/230 V AC, and 36 kA Icu at 380 V and 400/415 V AC, all 50/60 Hz per IEC 60947-2.

What standards does the EZC400N44400 comply with?

It complies with EN/IEC 60947-2, EN/IEC 60947-1, JIS C8201-2-2, and GB/T 14048.2. It is also marked suitable for isolation per IEC 60947-2.

MPN