Skip to main content
Schneider Electric EZC630H3600N — Miniature Circuit Breakers (MCB)

Schneider Electric EZC630H3600N EasyPact EZC630H Circuit Bre

MPNEZC630H3600N
Active

Schneider Electric EasyPact EZC630H, circuit breaker, 630 A at 40 °C, 3P, TM-D thermal-magnetic trip unit, 50 kA Icu at 380 V AC, fixed mount, IP20.

Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Aug 2026

Specifications

EZC630H3600N — Identification
ParameterValue
Product range (series)EasyPact
Product/component typeCircuit breaker
Device applicationDistribution
EZC630H3600N — Ratings
ParameterValue
Rated current (In)630 A at 40 °C
Poles configuration3P
Breaking capacity50 kA Icu at 380 V AC 50/60 Hz conforming to IEC 60947-2 50 kA Icu at 440 V AC 50/60 Hz conforming to IEC 60947-2 70 kA Icu at 220/230 V AC 50/60 Hz conforming to IEC 60947-2 50 kA Icu at 400/415 V AC 50/60 Hz conforming to IEC 60947-2
Rated service breaking capacity (Ics)25 kA at 440 V AC 50/60 Hz conforming to IEC 60947-2 70 kA at 220/230 V AC 50/60 Hz conforming to IEC 60947-2 50 kA at 380 V AC 50/60 Hz conforming to IEC 60947-2 50 kA at 400/415 V AC 50/60 Hz conforming to IEC 60947-2
Rated operational voltage (Ue)440 V AC 50/60 Hz conforming to IEC 60947-2
Rated insulation voltage (Ui)690 V AC 50/60 Hz conforming to IEC 60947-2
Rated impulse withstand voltage (Uimp)6 kV conforming to IEC 60947-2
Network type (AC/DC)AC
Network frequency50/60 Hz
Utilisation categoryCategory A
EZC630H3600N — Protection
ParameterValue
Trip unit technologyThermal-magnetic
Earth-leakage protectionWithout
Suitability for isolationYes conforming to IEC 60947-2
Electrical durability (cycles)Category A: 3000 cycles 415 V AC 50/60 Hz conforming to IEC 60947-2
Mechanical durability (cycles)10000 cycles
EZC630H3600N — Mechanical
ParameterValue
Mounting supportBackplate
Mounting modeFixed
Control typeToggle
Contact position indicatorYes
Local signalling/indicationPositive contact indication
Width140 mm
Height255 mm
Depth110 mm
EZC630H3600N — Environmental
ParameterValue
Operating ambient temperature-25...70 °C
Storage ambient temperature-35...85 °C
IP degree of protectionIP20 conforming to IEC 60529
Pollution degree3 conforming to IEC 60947
EZC630H3600N — Approvals
ParameterValue
StandardsEN/IEC 60947-2 GB/T 14048.2 JIS C8201-2-2 EN/IEC 60947-1

Product details

The EZC630H3600N is a 3-pole EasyPact EZC630H circuit breaker rated 630 A at 40 °C (In) with a TM-D thermal-magnetic trip unit. Breaking capacity is 50 kA Icu at 380 V AC, 50 kA at 400/415 V AC, and 50 kA at 440 V AC per IEC 60947-2. At 220/230 V AC it rises to 70 kA Icu. The 'H' breaking capacity code indicates the high-interrupting version — suitable for installations with high available fault current, such as industrial switchboards close to a transformer. This breaker is category A (no intentional short-time delay), with electrical endurance of 3000 cycles at 415 V AC and mechanical endurance of 10000 cycles. The IP20 finger-safe enclosure and IK07 impact resistance allow installation in accessible indoor panels where accidental contact or light mechanical impact is a concern.

The breaker complies with EN/IEC 60947-2, GB/T 14048.2, and JIS C8201-2-2 standards. No earth-leakage protection module is integrated (without), so any ground-fault protection must be added externally if required.

Fixed-mount design for backplate installation — no DIN-rail adapter. Dimensions: 255 mm height, 140 mm width, 110 mm depth. The 45 mm connection pitch between poles matches standard busbar spacing for 3-pole distribution blocks. The toggle control provides positive contact indication, so the operator can visually confirm the contact position.

Frequently asked questions

Who supplies EZC630H3600N and how is it quoted for volume purchases?

The EZC630H3600N is sourced through independent industrial-automation distribution channels. It is quoted to order against an RFQ; availability and current pricing are confirmed at quote time.

What is EZC630H3600N's breaking capacity at 400 V AC?

The breaking capacity is 50 kA Icu at 400/415 V AC per IEC 60947-2. At 380 V AC it is also 50 kA, and at 440 V AC it remains 50 kA. At 220/230 V AC the rating rises to 70 kA Icu.

What compliance documentation does this breaker carry?

The EZC630H3600N complies with EN/IEC 60947-2, GB/T 14048.2, and JIS C8201-2-2. It is rated for pollution degree 3 per IEC 60947 and carries IP20 finger-safe protection and IK07 impact resistance.

MPN
EZC630H3600N