Skip to main content
Schneider Electric EZC630N4400N — Circuit Breaker Accessories

Schneider Electric EZC630N4400N EasyPact EZC630N, 630 A, 36

MPNEZC630N4400N
Obsolete

Schneider Electric EasyPact EZC630N, EZC630N4400N, 4-pole circuit breaker, 630 A at 40 °C, 36 kA Icu at 440 V AC, thermal-magnetic TM-D trip unit, fixed mounting, IP20.

Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Jul 2026

Specifications

EZC630N4400N — Identification
ParameterValue
Product / component typeCircuit breaker
Range of productEasyPact
Device applicationDistribution
EZC630N4400N — Electrical
ParameterValue
Network type (AC/DC)AC
Rated current [In]630 A at 40 °C
Rated operational voltage [Ue]440 V AC 50/60 Hz conforming to IEC 60947-2
Rated insulation voltage [Ui]690 V AC 50/60 Hz conforming to IEC 60947-2
Rated impulse withstand voltage [Uimp]6 kV conforming to IEC 60947-2
Network frequency50/60 Hz
Poles description4P
EZC630N4400N — Protection & Performance
ParameterValue
Breaking capacity36 kA Icu at 440 V AC 50/60 Hz conforming to IEC 60947-2 40 kA Icu at 220/230 V AC 50/60 Hz conforming to IEC 60947-2 36 kA Icu at 380 V AC 50/60 Hz conforming to IEC 60947-2 36 kA Icu at 400/415 V AC 50/60 Hz conforming to IEC 60947-2
Rated service breaking capacity [Ics]18 kA at 440 V AC 50/60 Hz conforming to IEC 60947-2 40 kA at 220/230 V AC 50/60 Hz conforming to IEC 60947-2 36 kA at 380 V AC 50/60 Hz conforming to IEC 60947-2 36 kA at 400/415 V AC 50/60 Hz conforming to IEC 60947-2
Breaking capacity codeN
Trip unit technologyThermal-magnetic
Trip unit rating400 A at 50 °C
Trip unit nameTM-D
Protection typeOverload protection Short-circuit protection
Earth-leakage protectionWithout
Suitability for isolationYes conforming to IEC 60947-2
Utilisation categoryCategory A
Mechanical durability10000 cycles
Electrical durabilityCategory A: 3000 cycles 415 V AC 50/60 Hz conforming to IEC 60947-2
Local signallingPositive contact indication
Contact position indicatorYes
EZC630N4400N — Mechanical
ParameterValue
Connection pitch44 mm
Downside connectionFront
Upside connectionFront
Device short nameEasypact EZC630N
Control typeToggle
Mounting modeFixed
Mounting supportBackplate
Width185 mm
Height255 mm
Depth140 mm
ColourBlack
EZC630N4400N — Environmental
ParameterValue
IP degree of protectionIP20 conforming to IEC 60529
IK degree of protectionIK07 conforming to EN 50102
Pollution degree3 conforming to IEC 60947
Operating ambient air temperature-25...70 °C
Storage ambient air temperature-35...85 °C
EZC630N4400N — Approvals
ParameterValue
StandardsJIS C8201-2-2 EN/IEC 60947-2 EN/IEC 60947-1 GB/T 14048.2

Product details

The Schneider Electric EZC630N4400N is a 4-pole EasyPact EZC630N circuit breaker rated 630 A at 40 °C with a TM-D thermal-magnetic trip unit. It is marked Category A, meaning it is not intended for selective coordination with other breakers in series — plan for full discrimination upstream if needed.

Deployment context

This breaker mounts fixed to a backplate with front-front connections — no DIN-rail clip, so panel layout needs dedicated mounting holes and busbar takeoffs. The 185 mm width and 255 mm height determine the cutout and enclosure fill factor. IP20 means finger-safe but not washdown; install inside a locked panel. IK07 gives basic impact resistance for the enclosure face.

Designed and tested to EN/IEC 60947-2 (circuit-breaker standard), EN/IEC 60947-1 (general rules), JIS C8201-2-2, and GB/T 14048.2.

Frequently asked questions

How do I get current pricing and availability for EZC630N4400N?

Submit an RFQ through this listing. Availability and current pricing are confirmed at quote time through independent distribution channels.

What is the breaking capacity of EZC630N4400N at 440 V?

36 kA Icu at 440 V AC 50/60 Hz per IEC 60947-2. At 220/230 V it is 40 kA; at 380 V and 400/415 V it is also 36 kA.

What does the TM-D trip unit mean?

TM-D is a thermal-magnetic trip with fixed magnetic setting at 5000 A. The thermal element provides overload protection; the magnetic element handles short-circuit protection. No earth-leakage protection is built in.

MPN