Skip to main content
Schneider Electric EZC630N44600N

Schneider Electric EZC630N44600N EasyPact EZC630N, 630 A, 36

MPN EZC630N44600N
Obsolete

Schneider Electric EasyPact EZC630N, molded case circuit breaker, 630 A, 4P, TM-D thermal-magnetic trip unit, 36 kA Icu at 440 V AC.

Dispatch SLA24-48h Global Rush
Quality CheckOriginal Seal & Physical QC
IncotermsDAP / DDP Available
Source DocumentedChannel stated on listing & quote
Condition PhotosReal unit photos / video on request
WhatsApp AnswersFast human replies for machine-down parts
Worldwide DispatchDHL/FedEx — transit quoted per order
Independent China distributor & stockist· Listing updated Sep 2026

Specifications

EZC630N44600N key specifications
ParameterValue
Control typeToggle
Trip unit typeThermal-magnetic
Main product or component typeCircuit breaker
Voltage440 V AC 50/60 Hz conforming to IEC 60947-2
Insulation voltage ui690 V AC 50/60 Hz conforming to IEC 60947-2
Breaking capacity36 kA Icu at 440 V AC 50/60 Hz conforming to IEC 60947-2 40 kA Icu at 220/230 V AC 50/60 Hz conforming to IEC 60947-2 36 kA Icu at 380 V AC 50/60 Hz conforming to IEC 60947-2 36 kA Icu at 400/415 V AC 50/60 Hz conforming to IEC 60947-2
IP ratingIP20
Terminal pitch45 mm
Connection surface topFront
Connection surface bottomFront
Temp storage max85 °C
Temp storage min-35 °C

All specifications

EZC630N44600N additional specifications
ParameterValue
Temp operating max70 °C
Temp operating min-25 °C
Storage temperature-35...85 °C
Pollution degree3 conforming to IEC 60947
ColorBlack
Depth140 mm
Width140 mm
Height255 mm
Electrical life cyclesCategory A: 3000 cycles 415 V AC 50/60 Hz conforming to IEC 60947-2
Mechanical life cycles10000 cycles
ApplicationDistribution
Operating temperature-25...70 °C

Product details

The Schneider Electric EZC630N44600N is a 4-pole EasyPact EZC630N molded case circuit breaker rated 630 A at 40 °C, with a TM-D thermal-magnetic trip unit. Its 36 kA Icu at 440 V AC (50/60 Hz) per IEC 60947-2 means it can safely interrupt fault currents up to that level on a 400 V distribution bus without upstream coordination failure — the spec that decides whether this breaker clears a bolted fault or lets it cascade. The N breaking capacity code positions it for commercial and light industrial distribution panels, not heavy industrial high-fault locations.

Magnetic tripping current is 5000 A, so the instantaneous trip threshold is set at roughly 8× In — typical for thermal-magnetic MCCBs protecting distribution feeders against bolted faults while riding through motor inrush. The 36 kA Icu at 440 V AC is the maximum interrupting rating; at 400/415 V it holds at 36 kA, and at 220/230 V it rises to 40 kA. Electrical durability is 3000 cycles at 415 V AC in Category A (non-frequent switching). Mechanical durability is 10,000 cycles. For a distribution MCCB that sees occasional switching, this is adequate; for frequent load-break duty, a contactor should handle the switching cycles. If selectivity is required, a Category B breaker (with intentional delay) is needed upstream.

Fixed mounting on a backplate, with front-front connections (line and load both front-accessible). Dimensions are 255 mm high × 140 mm wide × 140 mm deep. IP20 finger-safe protection on the front cover; IK07 impact resistance.

MPN
EZC630N44600N