Skip to main content
Schneider Electric EZCV250H3080 — Molded Case Circuit Breakers (MCCB)

Schneider Electric EZCV250H3080 EasyPact MCCB, 80 A, 100 kA,

MPNEZCV250H3080
Obsolete

Schneider Electric EasyPact EZCV250H, 80 A, 3-pole, thermal-magnetic MCCB, 100 kA Icu at 240 V AC, TM-D trip unit, IP20, IEC 60947-2.

Source DocumentedChannel stated on listing & quote
Condition PhotosReal unit photos / video on request
WhatsApp AnswersFast human replies for machine-down parts
Worldwide DispatchDHL/FedEx — transit quoted per order
Independent China distributor & sourcing agent· Listing updated Sep 2026

Specifications

EZCV250H3080 — Identification
ParameterValue
Product / component typeCircuit breaker
Device applicationDistribution
EZCV250H3080 — Mechanical
ParameterValue
Height165 mm
Width105 mm
Depth68 mm
EZCV250H3080 — Electrical
ParameterValue
[In] rated current80 A at 40 °C
Breaking capacity100 kA Icu at 220...240 V AC 50/60 Hz conforming to IEC 60947-2 25 kA Icu at 440 V AC 50/60 Hz conforming to IEC 60947-2 36 kA Icu at 380...415 V AC 50/60 Hz conforming to IEC 60947-2
[Ics] rated service breaking capacity12.5 kA at 440 V AC 50/60 Hz conforming to IEC 60947-2 18 kA at 380...415 V AC 50/60 Hz conforming to IEC 60947-2 50 kA at 220...240 V AC 50/60 Hz conforming to IEC 60947-2
[Ue] rated operational voltage440 V AC 50/60 Hz conforming to IEC 60947-2
[Ui] rated insulation voltage440 V AC 50/60 Hz conforming to IEC 60947-2
EZCV250H3080 — Specifications
ParameterValue
Poles description3P
Trip unit nameTM-D
Trip unit technologyThermal-magnetic
Device short nameEasypact EZCV250H
StandardsEN/IEC 60947-2 JIS C8201-2-2 GB/T 14048.2 EN/IEC 60947-1

Product details

What this 80 A MCCB delivers for a distribution panel

The Schneider Electric EZCV250H3080 is a 3-pole EasyPact EZCV250H moulded-case circuit breaker with a TM-D thermal-magnetic trip unit rated 80 A at 40 °C. At 380–415 V AC the breaking capacity is 36 kA Icu, and at 440 V AC it's 25 kA Icu, so the voltage at the point of installation governs the rating you design to.

Fixed-mount, backplate installation. The 105 mm width and 165 mm height fit standard EasyPact cutout patterns; depth is 68 mm. Connection pitch is 35 mm, and both line and load connections are front-accessible — no need to reach behind the panel. IP20 finger-safe terminals keep live parts covered during commissioning.

Frequently asked questions

What is the breaking capacity of EZCV250H3080 at different voltages?

100 kA Icu at 220–240 V AC, 36 kA Icu at 380–415 V AC, and 25 kA Icu at 440 V AC, all per IEC 60947-2. The rating you design to depends on the actual line voltage at the installation point.

What standards does EZCV250H3080 comply with?

EN/IEC 60947-2, JIS C8201-2-2, and GB/T 14048.2 — covering European, Japanese, and Chinese regulatory frameworks. It also carries an IK07 impact rating and IP20 finger-safe protection.

MPN
EZCV250H3080