Skip to main content
Schneider Electric EZCV250H3150 — Molded Case Circuit Breakers (MCCB)

Schneider Electric EZCV250H3150 EasyPact MCCB, 150 A, 3P, TM

MPNEZCV250H3150
Obsolete

Schneider Electric EasyPact EZCV250H series, EZCV250H3150, molded case circuit breaker, 3P, 150 A at 40 °C, TM-D trip unit, 100 kA Icu at 240 V AC, 36 kA at 415 V, 25 kA at 440 V, IP20, front-connected.

Source DocumentedChannel stated on listing & quote
Condition PhotosReal unit photos / video on request
WhatsApp AnswersFast human replies for machine-down parts
Worldwide DispatchDHL/FedEx — transit quoted per order
Independent China distributor & sourcing agent· Listing updated Sep 2026

Specifications

EZCV250H3150 — Identification
ParameterValue
Product / component typeCircuit breaker
Device applicationDistribution
EZCV250H3150 — Mechanical
ParameterValue
Height165 mm
Width105 mm
Depth68 mm
EZCV250H3150 — Electrical
ParameterValue
[In] rated current150 A at 40 °C
Breaking capacity100 kA Icu at 220...240 V AC 50/60 Hz conforming to IEC 60947-2 25 kA Icu at 440 V AC 50/60 Hz conforming to IEC 60947-2 36 kA Icu at 380...415 V AC 50/60 Hz conforming to IEC 60947-2
[Ics] rated service breaking capacity12.5 kA at 440 V AC 50/60 Hz conforming to IEC 60947-2 18 kA at 380...415 V AC 50/60 Hz conforming to IEC 60947-2 50 kA at 220...240 V AC 50/60 Hz conforming to IEC 60947-2
[Ue] rated operational voltage440 V AC 50/60 Hz conforming to IEC 60947-2
[Ui] rated insulation voltage440 V AC 50/60 Hz conforming to IEC 60947-2
EZCV250H3150 — Specifications
ParameterValue
Poles description3P
Trip unit nameTM-D
Trip unit technologyThermal-magnetic
Device short nameEasypact EZCV250H
StandardsJIS C8201-2-2 EN/IEC 60947-2 EN/IEC 60947-1 GB/T 14048.2

Product details

The EZCV250H3150 is a 3-pole molded case circuit breaker from the Schneider Electric EasyPact EZCV250H family, rated 150 A at 40 °C with a thermal-magnetic TM-D trip unit. The TM-D trip unit combines a thermal element for overload protection and a magnetic element for short-circuit protection, plus integrated earth-leakage protection, so it covers ground faults in the same package without an external module. Breaking capacity is 100 kA Icu at 220–240 V AC, 36 kA at 380–415 V, and 25 kA at 440 V AC, all per IEC 60947-2. Verify available fault current against the 440 V rating if your system runs at that voltage.

Standards compliance covers IEC 60947-2, EN/IEC 60947-1, JIS C8201-2-2, and GB/T 14048.2 — so it is accepted in European, Japanese, and Chinese installations.

Fixed mounting on a backplate — not DIN-rail snap-on. The 105 mm width and 165 mm height fit standard MCCB panel cutouts; depth is 68 mm including the front-connected terminals. Connection pitch is 35 mm, matching typical busbar or cable-lug spacing for 150 A class breakers. IP20 finger protection on the front face; the enclosure itself is IK07 rated for impact resistance per EN 50102. Mechanical durability is 10,000 cycles — typical for a distribution MCCB not used for frequent switching. If your application requires daily load switching, consider a contactor in series; this breaker is designed for protection and infrequent manual operation via the toggle handle.

Frequently asked questions

What is the breaking capacity of the EZCV250H3150 at different voltages?

100 kA Icu at 220–240 V AC, 36 kA at 380–415 V AC, and 25 kA at 440 V AC, all per IEC 60947-2. The 240 V rating is the highest; the 440 V figure is the one to check if your system runs at that voltage.

Does the EZCV250H3150 include earth-leakage protection?

Yes, earth-leakage protection is integrated into the breaker — no external module or relay required. It covers ground faults in addition to the thermal-magnetic overload and short-circuit protection.

MPN
EZCV250H3150