Schneider Electric EZCV250H3175 — Molded Case Circuit Breakers (MCCB)

Schneider Electric EZCV250H3175 EasyPact MCCB, 175 A, 100 kA

MPNEZCV250H3175
Obsolete

Schneider Electric EasyPact EZCV250H series, molded case circuit breaker, 3-pole, 175 A thermal-magnetic TM-D trip unit, 100 kA Icu at 240 V AC, IP20 finger-safe enclosure.

Source DocumentedChannel stated on listing & quote
Condition PhotosReal unit photos / video on request
WhatsApp AnswersFast human replies for machine-down parts
Worldwide DispatchDHL/FedEx — transit quoted per order
Independent China distributor & sourcing agent· Listing updated Sep 2026

Specifications

EZCV250H3175 — Identification
ParameterValue
Product / component typeCircuit breaker
Device applicationDistribution
EZCV250H3175 — Mechanical
ParameterValue
Height165 mm
Width105 mm
Depth68 mm
EZCV250H3175 — Electrical
ParameterValue
[In] rated current175 A at 40 °C
Breaking capacity100 kA Icu at 220...240 V AC 50/60 Hz conforming to IEC 60947-2 25 kA Icu at 440 V AC 50/60 Hz conforming to IEC 60947-2 36 kA Icu at 380...415 V AC 50/60 Hz conforming to IEC 60947-2
[Ics] rated service breaking capacity12.5 kA at 440 V AC 50/60 Hz conforming to IEC 60947-2 18 kA at 380...415 V AC 50/60 Hz conforming to IEC 60947-2 50 kA at 220...240 V AC 50/60 Hz conforming to IEC 60947-2
[Ue] rated operational voltage440 V AC 50/60 Hz conforming to IEC 60947-2
[Ui] rated insulation voltage440 V AC 50/60 Hz conforming to IEC 60947-2
EZCV250H3175 — Specifications
ParameterValue
Poles description3P
Trip unit nameTM-D
Trip unit technologyThermal-magnetic
Device short nameEasypact EZCV250H
StandardsJIS C8201-2-2 EN/IEC 60947-2 EN/IEC 60947-1 GB/T 14048.2

Product details

The Schneider Electric EZCV250H3175 is a 3-pole molded case circuit breaker from the EasyPact EZCV250H series, fitted with a TM-D thermal-magnetic trip unit rated at 175 A at 40 °C. This is the distribution-grade variant with earth-leakage protection integrated, intended for fixed-mount backplate installation in panelboards and switchboards. Breaking capacity is the headline selector here: 100 kA Icu at 220–240 V AC, 36 kA at 380–415 V, and 25 kA at 440 V — all per IEC 60947-2. That H breaking-capacity code means it handles high prospective fault currents at the lower distribution voltages common in commercial and light industrial mains, so it can be applied upstream without a current-limiting fuse for coordination.

The 105 mm width and 165 mm height fit standard panel cutouts for the EZCV250H frame. IP20 finger-safe enclosure per IEC 60529 and IK07 impact resistance per EN 50102.

Protection and Duty

Earth-leakage protection is onboard, so this single device covers overcurrent and ground-fault in one footprint — a space-saving choice compared to a separate RCCB plus MCCB combination.

Frequently asked questions

What is the closest alternative to EZCV250H3175 in the EasyPact family?

Within the same EZCV250H frame, the closest alternative is a variant with a different trip rating or without earth-leakage protection. The TM-D trip unit and H breaking-capacity code are consistent across the series; the deciding factor is the 175 A setting and the integrated earth-leakage function, which distinguishes this order code from the non-ELB versions.

What compliance documentation does Schneider provide for EZCV250H3175?

The breaker is certified to IEC 60947-2, IEC 60947-1, JIS C8201-2-2, and GB/T 14048.2. It is suitable for isolation per IEC 60947-2 and carries IP20 and IK07 ratings. RoHS and REACH declarations are available from the manufacturer upon request.

MPN
EZCV250H3175