Schneider Electric EZEUVR125DC — Miniature Circuit Breakers (MCB)

Schneider Electric EZEUVR125DC undervoltage release MN, 125

MPNEZEUVR125DC
Obsolete

Schneider Electric EasyPact EZC250/EZCV250 series, undervoltage release MN, 125 V DC control circuit voltage, operating threshold 0.35...0.7 Un opening 0.85 Un closing.

Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Jul 2026

Specifications

EZEUVR125DC — Identification
ParameterValue
Product rangeEasyPact
Product range (series)EZC250 EZCV250
Product/component typeVoltage release
Device applicationControl
EZEUVR125DC — Other specifications
ParameterValue
Device short nameMN
Operating threshold0.35...0.7 Un opening 0.85 Un closing
Voltage release typeUndervoltage release
Coil voltage125 V DC

Product details

The Schneider Electric EZEUVR125DC is an undervoltage release (device short name MN) for the EasyPact EZC250 and EZCV250 molded-case circuit breaker ranges. It drops the breaker when the control voltage falls below 0.35 to 0.7 Un and allows closing only when voltage returns above 0.85 Un — a standard undervoltage protection function for control circuits that need to prevent automatic reclosure after a dip or outage.

Control voltage and fit

Rated for a 125 V DC control circuit. The operating threshold is specified as 0.35...0.7 Un for opening and 0.85 Un for closing, so on a 125 V DC system the release trips when the voltage drops to roughly 44–88 V DC and resets above about 106 V DC. It mounts inside the EZC250 or EZCV250 breaker — no separate DIN-rail space needed, but the breaker itself occupies the panel cutout.

Frequently asked questions

Where can I buy EZEUVR125DC and how do I get a price?

We source the EZEUVR125DC through independent distribution channels. Submit an RFQ for current availability and pricing — confirmed at quote time, not a live stock figure.

What breakers does the EZEUVR125DC fit?

It fits the Schneider Electric EasyPact EZC250 and EZCV250 molded-case circuit breaker ranges.

What is the control voltage and operating threshold for EZEUVR125DC?

The control circuit voltage is 125 V DC. The undervoltage release opens the breaker when voltage falls to 0.35...0.7 Un (roughly 44–88 V DC) and allows closing when it rises above 0.85 Un (about 106 V DC).