It's built for distribution duty in fixed-mount panels — front-connected, backplate-mounted, with a 35 mm connection pitch.
The F breaking capacity code means 70 kA Icu at 220/240 V AC and 36 kA Icu at 380–440 V AC per IEC 60947-2. The 1250 kA integral instant protection on the magnetic element clears bolted faults fast — keeps let-through energy low enough to protect downstream terminals and busbars.
Fixed backplate mount, front connections both top and bottom. The 105 mm width and 161 mm height fit standard panel cutouts for 3-pole MCCBs in this class. Neutral position is left, which matters if you're wiring a 3P+N assembly. IK07 impact rating handles accidental tool drops during commissioning.
Certified to IEC 60947-2 and EN 60947-2. Electrical durability is 25,000 cycles at 415 V at half rated current per IEC 60947-2; mechanical durability is 25,000 cycles. Storage temperature range is -50 to 85 °C.