Skip to main content
Schneider Electric GS1AM111 — Auxiliary Contacts

Schneider TeSys GS1AM111 Auxiliary Contact, 1 C/O, 32 A

MPNGS1AM111
Obsolete

Schneider Electric TeSys GS1AM111 auxiliary contact block, 1 C/O early-break, side-mount for GS1 32A disconnector, 32 A switch rated current.

Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Jul 2026

Specifications

GS1AM111 — Identification
ParameterValue
Product typeAuxiliary contact
Product range / familyTeSys
GS1AM111 — Ratings
ParameterValue
Rated operational current (Ie), by utilization category5 A at 127 V AC-15 4 A at 230 V AC-15 3 A at 400/415 V AC-15 2 A at 440 V AC-15 12 A at 24 V DC-13 2 A at 48 V DC-13 0.6 A at 110 V DC-13 0.4 A at 220 V DC-13
Conventional free-air thermal current (Ith)16 A (at 40 °C)
GS1AM111 — Performance
ParameterValue
Mechanical durability (cycles)1 Mcycles
GS1AM111 — Other specifications
ParameterValue
Fuse typeNFC DIN BS
Contact operationEarly-break
Device short nameGS1AM
Mounting locationRight side
Contact applicationO and I position signalling
Switch rated current32 A
Electrical durability30000 cycles AC-15
Type of operating handleDirect frontal
Contacts type and composition1 C/O

Product details

The GS1AM111 is an auxiliary contact block from the Schneider TeSys GS1AM series, designed as a side-mount early-break contact for a GS1 32 A switch-disconnector with a direct frontal handle. It provides O and I position signalling — meaning it reports whether the main switch is open or closed, and the early-break contact opens before the main poles, which is useful for pilot circuits that must drop out ahead of the power circuit.

The contact block carries a 1 C/O (one changeover) configuration. The real-world switching capacity depends on the duty: in AC-15 (pilot duty for solenoid valves and contactor coils) it handles 5 A at 127 V, 4 A at 230 V, 3 A at 400/415 V, and 2 A at 440 V. For DC-13 (solenoid loads) it manages 12 A at 24 V, 2 A at 48 V, 0.6 A at 110 V, and 0.4 A at 220 V. The switch rated current of the main disconnector it mounts to is 32 A — the auxiliary block itself is not the main power path, but the 16 A Ith gives headroom for the signal circuit.

Mounting and integration note

Mounts on the right side of the GS1 32 A switch-disconnector. The direct frontal handle means the auxiliary block is actuated by the handle mechanism, not a separate linkage. In a panel, this clips onto the switch body and adds one C/O signal contact without increasing the DIN-rail footprint of the main device. The early-break function means this contact opens before the main poles close — wire the NC (normally closed) side into a safety or interlock circuit that must break before power reaches the load.

Frequently asked questions

What is the GS1AM111's fuse type?

The listed fuse type is NFC DIN BS, which refers to the fuse standard the associated disconnector accepts (NFC for French standard, DIN for German, BS for British). This is a characteristic of the main GS1 switch body, not the auxiliary contact itself.

What are the key ratings for the GS1AM111?

It is a 1 C/O auxiliary contact block with a conventional free-air thermal current of 16 A at 40 °C. For AC-15 pilot duty it is rated 5 A at 127 V, 4 A at 230 V, 3 A at 400/415 V, and 2 A at 440 V. For DC-13 solenoid duty it handles 12 A at 24 V, 2 A at 48 V, 0.6 A at 110 V, and 0.4 A at 220 V. Electrical durability is 30,000 cycles under AC-15; mechanical durability is 1 million cycles.

How do I source the GS1AM111 given it is obsolete?

Since Schneider lists it as Obsolete with no official successor, sourcing is through the surplus and new-old-stock channel. Submit an RFQ with your quantity; we source against available inventory from our multi-distributor network. No stock or lead-time number is carried here — it is a quoted-to-order part.

MPN
GS1AM111