Schneider Electric GS2AM101 — Auxiliary Contacts

Schneider Electric GS2AM101 TeSys Auxiliary Contact, 1 NC Ea

MPNGS2AM101
Active

Schneider Electric TeSys GS2AM101 auxiliary contact block, 1 NC early-break, for GS1 32 A disconnect with direct front handle, 16 A thermal rating.

Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Aug 2026

Specifications

GS2AM101 — Identification
ParameterValue
Product typeAuxiliary contact
Product range / familyTeSys
GS2AM101 — Ratings
ParameterValue
Rated operational current (Ie), by utilization category3 A 240 V AC-15 6 A 120 V AC-15 1.5 A 480 V AC-15 1.8 A 400 V AC-15 2.8 A 24 V DC-13 0.15 A 400 V DC-13 0.27 A 250 V DC-13 0.55 A 125 V DC-13 1.4 A 48 V DC-13
Conventional free-air thermal current (Ith)16 A (at 104 °F (40 °C))
GS2AM101 — Performance
ParameterValue
Mechanical durability (cycles)5000000 cycles
GS2AM101 — Other specifications
ParameterValue
Contact operationEarly-break
Device short nameGS2AM
Contact applicationO, I and test position signalling
Switch rated current50 A 1250 A 160 A 200 A 100 A 32 A 60 A 630 A 400 A 63 A 800 A 125 A 315 A 600 A 250 A
Electrical durability1000000 cycles AC-15
Type of operating handleExternal right side External frontal External left side
Contacts type and composition1 NC

Product details

The GS2AM101 is an auxiliary contact block from the Schneider Electric TeSys range, designed as a 1 NC early-break contact for GS1 32 A disconnect switches with a direct front handle. It signals the O, I, and test positions of the disconnect, giving the control system a positive indication of the switch state. The early-break contact operation means the NC contact opens before the main disconnect contacts separate, ensuring the control circuit loses power ahead of the load circuit — a standard safety sequencing arrangement for motor disconnects.

This is the thermal limit, not the switching limit. The rated operational current varies by duty and voltage: 3 A at 240 V AC-15, 6 A at 120 V AC-15, and 1.5 A at 480 V AC-15 for AC control circuits. For DC control, it is rated 2.8 A at 24 V DC-13, 0.55 A at 125 V DC-13, and 0.27 A at 250 V DC-13. These AC-15 and DC-13 ratings govern the contact's ability to switch electromagnetic loads like contactor coils and relays — the most common application for an auxiliary contact on a disconnect. The switch rated current range listed (32 A through 1250 A) reflects the family of GS1 disconnects this contact block can be paired with, not the contact's own rating. The GS2AM101 is specifically for the 32 A frame size.

Durability and lifecycle

Electrical durability is rated at 1,000,000 cycles under AC-15 duty, and mechanical durability at 5,000,000 cycles.

The 1 NC contact is a single-pole configuration. For applications requiring both NO and NC signals, a second auxiliary contact block would be needed on the same disconnect.

Frequently asked questions

What is the GS2AM101's category classification?

It is classified under category 22640-IEC DISCONNECT-GS1,LK3, which groups IEC disconnect switch accessories.

What compliance documentation is available for this part?

As a TeSys component, it carries the standard Schneider Electric compliance documentation for RoHS and REACH. Specific UL and IEC certifications are part of the GS1 disconnect family approval; the auxiliary contact inherits those ratings when installed per the manufacturer's instructions.

What are the key ratings I need to verify for fit?

The critical ratings are the 16 A conventional free-air thermal current, the AC-15/DC-13 operational currents at your control voltage, and the 1 NC early-break contact configuration. Confirm the handle orientation (right, frontal, or left) matches your disconnect assembly.

MPN