The GS2AM110 is an auxiliary contact block from the TeSys GS range, designed as a 1 NO early-break contact for the GS1 32 A disconnect switch with a direct front handle. It signals the O, I, and test positions of the disconnect, giving the control system a positive indication of switch state.
Rated operational current (Ie) covers both AC-15 and DC-13 loads: 6 A at 120 V AC-15, 3 A at 240 V AC-15, and 1.5 A at 480 V AC-15 — these are the inductive load ratings for solenoid and contactor coils typical in control circuits. For DC control, it handles 2.8 A at 24 V DC-13 and 0.55 A at 125 V DC-13, but drops to 0.15 A at 400 V DC-13.
Mounts on the left or right side of the GS1 disconnect, or on the front, using the external handle. The early-break contact opens before the main disconnect contacts, which is used to drop control power or signal a pending shutdown before the load circuit opens. Mechanical durability is rated at 5,000,000 cycles; electrical durability at 1,000,000 cycles under AC-15 duty.