Schneider Electric GV4LE02N — Motor Protection Circuit Breakers (MPCB)

Schneider Electric GV4LE02N TeSys Deca Motor Circuit Breaker

MPNGV4LE02N
Active

Schneider Electric TeSys Deca GV4L motor circuit breaker, GV4LE02N, 3-pole, 2 A rated current, magnetic-electronic trip, IP40, 100 kA breaking capacity.

$413.58Ref. price · indicative, final on quote
Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Aug 2026

Specifications

GV4LE02N — Mechanical
ParameterValue
Height155 mm
Width81 mm
Depth116 mm

Product details

The magnetic trip range spans 12…28 A, so short-circuit or locked-rotor events above that threshold cause instantaneous opening, protecting the motor and downstream cable. Breaking capacity reaches 100 kA Icu at 220…240 V AC and 50 kA at 380…415 V AC per IEC 60947-2. Rated for AC-3 duty per IEC 60947-4-1, so it handles the inrush of a squirrel-cage motor during starting and the switching of the running load.

IP40 protection means it is suited for indoor panel environments where tools or fingers are the main intrusion risk — no washdown tolerance. Operating temperature range is -25…70 °C, storage -50…85 °C. EverLink BTR screw terminals on top accept 1.5…70 mm² solid or 1.5…50 mm² flexible; bottom terminals accept 2.5…95 mm² solid or 2.5…70 mm² flexible. Tightening torque is 9 N·m for the larger cable range (16…95 mm²) and 5 N·m for 1.5…10 mm². The terminals are rated for 960 °C glow-wire test per IEC 60695-2-11.

Frequently asked questions

What is the breaking capacity of the GV4LE02N?

The GV4LE02N has a breaking capacity of 100 kA Icu at 220…240 V AC, 50 kA at 380…415 V AC, 50 kA at 440 V AC, 25 kA at 500 V AC, 15 kA at 525 V AC, and 8 kA at 660…690 V AC, all per IEC 60947-2.

What standards does the GV4LE02N comply with?

The GV4LE02N complies with EN/IEC 60947-2 (circuit-breaker standard) and EN/IEC 60947-4-1 (contactor and motor-starter standard). It is also suitable for isolation per IEC 60947-1.

What is the magnetic trip range on the GV4LE02N?

The magnetic tripping current is adjustable from 12 A to 28 A, providing short-circuit and locked-rotor protection for the motor branch circuit.