Rated at 2 A continuous (In), this breaker protects small motors — think fractional-horsepower pumps, fans, or conveyors — across a wide voltage range: it covers 0.25 kW at 400 V up to 1.5 kW at 690 V. That 2 A figure is the trip rating, not the load current you set it to; you'd dial it to match the motor's full-load amps, and the magnetic trip kicks in between 12 and 28 A for short-circuit protection.
The GV4LE02S6 carries a 120 kA Icu at 240 V AC, dropping to 100 kA at 415 V, 70 kA at 440 V, and 10 kA at 690 V. It meets both EN/IEC 60947-2 (circuit breaker standard) and EN/IEC 60947-4-1 (motor starter standard), so it's certified for motor branch circuit protection as a combined motor protector — not just a distribution breaker.
Panel integration and mechanical fit
Mounts in any position, so you're not locked into a specific orientation inside the enclosure. The 27 mm connection pitch without spreaders (35 mm with) matches typical motor starter layouts; you'll need ring-terminal lugs on the power cables, with a 9 N·m torque for the main terminals (16–95 mm² cable) and 5 N·m for the control terminals (1.5–10 mm²). IP40 front-of-panel protection, IK07 impact resistance — fine for a dry indoor cabinet, but not washdown-rated. The grey RAL 7016 housing is standard for the TeSys Deca line.