Schneider Electric GV4PEM115N — Motor Protection Circuit Breakers (MPCB)

Schneider Electric GV4PEM115N TeSys GV4 Motor Circuit

MPNGV4PEM115N
Active

Schneider Electric TeSys GV4 motor circuit breaker, GV4PEM115N, 115 A rated current, 3-pole, electronic thermal-magnetic trip, 100 kA breaking capacity at 240 V AC, IP40, gray RAL 7016.

$982.06 – $1,225.57Ref. price · indicative, final on quote
Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Aug 2026

Specifications

GV4PEM115N — Mechanical
ParameterValue
Height6.1 in (155 mm)
Width3.2 in (81 mm)
Depth4.6 in (116 mm)

Product details

Active production, 115 A motor circuit breaker for 37–110 kW range

The GV4PEM115N: The electronic thermal-magnetic trip unit combines adjustable overload protection with a fixed magnetic trip set at 1955 A — 17× In — so it clears short-circuits fast without nuisance tripping on motor inrush. Phase-failure sensitivity per IEC 60947-4-1 means it drops the load when one phase opens, preventing single-phasing damage.

Under UL 60947 it delivers 65 kA at 240 V and 35 kA at 480Y/277 V.

DIN-rail footprint and EverLink terminals — panel build notes

The GV4PEM115N measures 155 mm high × 81 mm wide × 116 mm deep — a compact 3-pole footprint that clips onto standard DIN rail. The EverLink BTR screw terminals accept solid copper up to 95 mm² on the load side and 70 mm² on the line side, with a tightening torque of 9 N·m for the main power connections. That's enough cross-section for the 115 A feed without parallel conductors. IP40 enclosure with IK07 impact resistance handles normal panel environments; the gray RAL 7016 housing is the standard industrial finish. Power dissipation is 4.6 W per pole at rated current — about 14 W total for the three poles — so thermal rise inside a sealed enclosure stays manageable without forced ventilation.

Electrical and mechanical endurance — cycle life for frequent starting

For a motor starter seeing frequent starts — conveyors, pumps, compressors — that translates to years of service before contact maintenance is needed. Shock rating is 15 gn for 11 ms. The breaker holds calibration and trip accuracy under these conditions, which matters for mobile equipment or machinery mounted near rotating unbalance.

Frequently asked questions

What compliance documentation does this brand provide for GV4PEM115N?

Fire resistance is tested to 960 °C per IEC 60695-2-11. Climatic withstand follows IACS. Documentation typically includes the declaration of conformity and UL/CSA file numbers.

MPN
GV4PEM115N