Skip to main content
Schneider Electric GV4PEM50B

Schneider GV4PEM50B TeSys Deca Motor Circuit Breaker, 50 A

MPN GV4PEM50B
Obsolete

Schneider Electric TeSys Deca GV4PEM50B motor circuit breaker, 3-pole, 50 A, thermal-magnetic trip, 50 kA breaking capacity at 240 V, IP40, gray RAL 7016.

$892.00 Ref. price · indicative, final on quote
Dispatch SLA24-48h Global Rush
Quality CheckOriginal Seal & Physical QC
IncotermsDAP / DDP Available
Source DocumentedChannel stated on listing & quote
Condition PhotosReal unit photos / video on request
WhatsApp AnswersFast human replies for machine-down parts
Worldwide DispatchDHL/FedEx — transit quoted per order
Independent China distributor & stockist· Listing updated Sep 2026

Specifications

GV4PEM50B key specifications
ParameterValue
Control typeToggle
Trip unit typeThermal-magnetic Electronic
Main product or component typeMotor circuit breaker
Voltage690 V AC 50/60 Hz IEC 60947-2
Insulation voltage ui800 V AC 50/60 Hz IEC 60947-2
Breaking capacity50 kA Icu 220...240 V AC 50/60 Hz IEC 60947-2 25 kA Icu 380...415 V AC 50/60 Hz IEC 60947-2 20 kA Icu 440 V AC 50/60 Hz IEC 60947-2 10 kA Icu 500 V AC 50/60 Hz IEC 60947-2 35 kA 208Y/120 V AC 50/60 Hz UL 60947 35 kA 240 V AC 50/60 Hz UL 60947 18 kA 480Y/277 V AC 50/60 Hz UL 60947 14 kA 600Y/347 V AC 50/60 Hz UL 60947
Utilization categoryCategory A IEC 60947-2 AC-3 IEC 60947-4-1
IP ratingIP40
Temp storage max85 °C
Temp storage min-50 °C
Temp operating max70 °C
Temp operating min-25 °C

All specifications

GV4PEM50B additional specifications
ParameterValue
Storage temperature-58...185 °F (-50...85 °C)
Pollution degree3
ColorGray RAL 7016)
Depth4.6 in (116 mm)
Width3.2 in (81 mm)
Height6.1 in (155 mm)
Electrical life cycles20000 cycles AC-3 440 V In/2 10000 cycles AC-3 440 V In
Mechanical life cycles40000 cycles
ApplicationMotor protection
Operating positionAny position
Operating temperature-13...158 °F (-25...70 °C)

Product details

50 A motor branch circuit protection with dual trip technology

The GV4PEM50B: Phase failure sensitivity per IEC 60947-4-1 is built in — the breaker trips on loss of one phase, preventing single-phase motor burnout. Suitability for isolation per IEC 60947-1 means this device can serve as a disconnecting means in the motor branch, eliminating a separate disconnect switch.

Breaking capacity and voltage selection

Under UL 60947, it delivers 35 kA at 240 V and 18 kA at 480Y/277 V. Motor power ratings span 11 kW at 400 V to 45 kW at 690 V, with multiple intermediate steps — confirm the kW column for your supply voltage before specifying.

Panel fit and environmental ratings

Dimensions are 3.2 in wide, 6.1 in high, 4.6 in deep (81 × 155 × 116 mm) — fits standard motor control center buckets and DIN-rail enclosures. IP40 protection suits clean indoor panels; IK07 impact rating resists incidental tool strikes. Operating altitude up to 5000 m without derating, and any mounting position is allowed — useful for tight enclosures where vertical orientation isn't possible. EverLink BTR screw terminals accept up to 95 mm² solid on the bottom and 70 mm² flexible on top — torque to 9 N·m for the main conductors.

MPN
GV4PEM50B