Skip to main content
Schneider Electric GV4PEM80S6

Schneider Electric GV4PEM80S6 TeSys GV4 MPCB, 80 A, 120 kA

MPN GV4PEM80S6
Obsolete

Schneider Electric TeSys GV4 motor circuit breaker, 80 A rated current, 3-pole, electronic thermal-magnetic trip, 120 kA breaking capacity at 240 V AC, IP40, gray RAL 7016.

Dispatch SLA24-48h Global Rush
Quality CheckOriginal Seal & Physical QC
IncotermsDAP / DDP Available
Source DocumentedChannel stated on listing & quote
Condition PhotosReal unit photos / video on request
WhatsApp AnswersFast human replies for machine-down parts
Worldwide DispatchDHL/FedEx — transit quoted per order
Independent China distributor & stockist· Listing updated Sep 2026

Specifications

GV4PEM80S6 key specifications
ParameterValue
Control typeToggle
Trip unit typeElectronic Thermal-magnetic
Main product or component typeMotor circuit breaker
Voltage690 V AC 50/60 Hz IEC 60947-2
Insulation voltage ui800 V AC 50/60 Hz IEC 60947-2
Utilization categoryCategory A IEC 60947-2 AC-3 IEC 60947-4-1
IP ratingIP40
Terminal pitch1.06 in (27 mm) without spreaders 1.4 in (35 mm) with spreaders
Temp storage max85 °C
Temp storage min-50 °C
Temp operating max70 °C
Temp operating min-25 °C

All specifications

GV4PEM80S6 additional specifications
ParameterValue
Storage temperature-58...185 °F (-50...85 °C)
Pollution degree3
ColorGray RAL 7016)
Depth4.6 in (116 mm)
Width3.2 in (81 mm)
Height6.1 in (155 mm)
Electrical life cycles14000 cycles AC-3 440 V In/2 7000 cycles AC-3 440 V In
Mechanical life cycles40000 cycles
ApplicationMotor protection
Operating positionAny position
Operating temperature-13...158 °F (-25...70 °C)

Product details

80 A motor circuit breaker, TeSys GV4 frame

The GV4PEM80S6 is a 3-pole motor circuit breaker from the TeSys GV4 range, rated 80 A continuous with an electronic thermal-magnetic trip unit. It is listed to UL 60947-4-1 and IEC 60947-4-1, making it suitable for motor protection in both North American and IEC-distribution panels.

Trip coordination and motor protection

The electronic thermal-magnetic trip provides adjustable overload protection (via the TeSys GV4 dial) plus a fixed magnetic trip at 1360 A — 17× In, which avoids nuisance trips on high-inrush motor starts while clearing bolted faults fast. Phase-failure sensitivity per IEC 60947-4-1 is built in, so a lost phase on the line side trips the breaker before the motor single-phases to destruction. Mechanical durability is 40,000 cycles — the breaker is designed for frequent start/stop applications on conveyors, pumps, and compressors.

Panel fit and environmental ratings

Dimensions are 6.1 in (155 mm) high × 3.2 in (81 mm) wide × 4.6 in (116 mm) deep, with a connection pitch of 27 mm without spreaders or 35 mm with spreaders. The gray RAL 7016 housing carries IP40 protection (finger-safe) and IK07 impact resistance, so it withstands incidental tool contact in an open panel. Terminals accept lug/ring connections up to 95 mm² (0.02–0.1 in²) with a tightening torque of 9 N·m.

MPN