Skip to main content
Schneider Electric GVAE1TQ — Auxiliary Contacts

Schneider GVAE1TQ Auxiliary Contact Block, TeSys Deca, 1NO/N

MPNGVAE1TQ
Active

Schneider Electric TeSys Deca GVAE1TQ auxiliary contact block, 1NO/NC, front mounting for GV2 manual starters, bulk quantity set of 24.

Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Aug 2026

Specifications

GVAE1TQ — Identification
ParameterValue
Product typeAuxiliary contact block
Product range / familyTeSys TeSys Deca
GVAE1TQ — Ratings
ParameterValue
Conventional free-air thermal current (Ith)2.5 A
Rated operational voltage (Ue)24...240 V AC 24...60 V DC
GVAE1TQ — Performance
ParameterValue
Rated insulation voltage (Ui)300 V conforming to UL 508 300 V conforming to CSA C22.2 No 14 250 V conforming to IEC 60947-1
Mechanical durability (cycles)100000 cycles
GVAE1TQ — Mechanical
ParameterValue
Terminal tightening torque1.7 N.m screw clamp terminals
Width45 mm
Height11 mm
Depth29 mm
GVAE1TQ — Approvals
ParameterValue
StandardsEN/IEC 60947-5-1 UL 60947-4-1 CSA C22.2 No 60947-4-1 IEC/EN 60335-1:Clause 30.2 IEC/EN 60335-2-40:Annex JJ

Product details

The GVAE1TQ is a front-mount auxiliary contact block from the TeSys Deca range, designed to snap onto the side of a GV2 manual starter or motor-protective circuit breaker. It adds one NO and one NC set of contacts, giving you a feedback signal or control interlock without wiring a separate relay. The 29 mm depth keeps the assembly compact on the DIN rail — no extra panel space needed beyond the starter itself. Rated for 2.5 A conventional free-air thermal current and a minimum switching capability of 5 mA at 17 V, so it handles both the PLC input and the small-signal pilot duty without contact wetting issues. Mechanical durability is rated at 100,000 cycles — that's the life of the block itself, not the motor starter it rides on.

The AC-15 and DC-13 ratings tell you the block is tested for switching electromagnetic loads — contactors, relays, solenoid valves — not just resistive heaters. At 230 V AC it's rated for 120 VA, which covers most small contactor coils. On the DC side, you get 24 W at 24 V DC-13, enough for a PLC output driving a holding coil or a brake solenoid. The 48 V DC-13 rating drops to 15 W, so watch your voltage drop on longer cable runs. Insulation coordination is rated 300 V per UL 508 and CSA C22.2 No 14, with a 250 V rating under IEC 60947-1. That's fine for 240 V line-to-line control circuits in North America and 230/400 V systems globally, as long as the phase-to-ground voltage stays within limits. The standards list includes EN/IEC 60947-5-1 (control circuit devices), UL 60947-4-1 and CSA C22.2 No 60947-4-1 (contactors and starters), plus IEC/EN 60335-1 and -2-40 for appliance and heat-pump applications — so it's certified for both industrial panels and HVAC equipment.

Compliance documentation is covered by the UL, CSA, and IEC standards listed on the product label. RoHS and REACH declarations are standard for Schneider's current TeSys portfolio — the part carries the CE mark by virtue of the IEC standards. No separate documentation request should be needed for a standard industrial panel build.

Frequently asked questions

What is the closest pin-compatible alternative to the GVAE1TQ?

There is no pin-compatible alternative because this is the current active part. The GVAE1TQ is the standard front-mount auxiliary contact block for GV2 starters in the TeSys Deca range. If you need a different contact configuration, look at other GVAE blocks in the same family, but the mounting and wiring footprint are specific to this series.

What is the GVAE1TQ's depth?

The GVAE1TQ has a depth of 29 mm. This keeps the assembly compact on the DIN rail when mounted to a GV2 starter.

What range is the GVAE1TQ part of?

The GVAE1TQ belongs to the TeSys Deca range, specifically designed for use with GV2 manual starters and motor-protective circuit breakers.

What compliance documentation does Schneider provide for the GVAE1TQ?

The GVAE1TQ carries certifications to EN/IEC 60947-5-1, UL 60947-4-1, CSA C22.2 No 60947-4-1, and IEC/EN 60335-1 and -2-40 (appliance and heat-pump standards). RoHS and REACH declarations are standard for current Schneider TeSys products. No separate documentation request should be needed for standard industrial or HVAC panel builds.

MPN