Skip to main content
Schneider Electric GVAS416 — Motor Protection Circuit Breakers (MPCB)

Schneider GVAS416 TeSys Shunt Trip Release, 415V AC 60Hz

MPNGVAS416
Obsolete

Schneider Electric TeSys Deca GVAS416 shunt trip release (MX), 415V AC 60Hz control circuit, 690V rated insulation, screw clamp terminals.

Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Jul 2026

Specifications

GVAS416 — Mechanical
ParameterValue
Height89 mm
Width18 mm
Depth66 mm

Product details

The GVAS416 is a shunt trip release (MX) from the Schneider Electric TeSys Deca range, designed to remotely trip a TeSys motor starter on command. It operates on a 415 V AC 60 Hz control circuit and is rated for insulation up to 690 V AC per IEC 60947-1, with UL/CSA recognition at 600 V AC.

The release mounts directly onto compatible TeSys Deca starters (GV2ME, GV2P, GV3P, GV3L). Dimensions are 18 mm wide, 89 mm high, 66 mm deep — a narrow footprint that fits into a crowded DIN-rail enclosure without stealing space from adjacent poles. Screw clamp terminals accept 1 to 2.5 mm² solid or 0.75 to 2.5 mm² flexible wire; torque to under 1.4 N·m. Mechanical durability is rated at 10,000 cycles with GV3P/GV3L and 30,000 cycles with GV2ME/GV2P.

Electrical characteristics

Inrush power is 10.5 W / 14 VA AC; holding power drops to 1.6 W / 5 VA AC after the coil seals. The control circuit operates between 0.7 and 1.1 times nominal voltage (Un), with a tripping threshold of 0.75 to 0.2 Un — meaning it will reliably drop out when the control voltage sags below about 311 V AC on a 415 V line. On-load factor is 100 %, so it can remain energized continuously without derating.

Frequently asked questions

What is the closest replacement for GVAS416?

There is no official direct-replacement order code from the manufacturer for this specific obsolete part. For a new design, select a current TeSys shunt trip release with the same control voltage (415 V AC 60 Hz) and mechanical interface for your starter frame.

What are the key ratings of GVAS416?

Control voltage is 415 V AC 60 Hz. Rated insulation voltage is 690 V AC (IEC) / 600 V AC (UL/CSA). Operating time is 10 to 15 ms. Mechanical durability ranges from 10,000 to 30,000 cycles depending on the starter model.

How do I source GVAS416?

Since it is obsolete, we source it to order against an RFQ through surplus and authorized aftermarket channels. Submit an RFQ for current availability and pricing.

MPN
GVAS416