Schneider Electric GVAU055 — Motor Protection Circuit Breakers (MPCB)

GVAU055 TeSys Deca Undervoltage Release, 48V AC 50Hz

MPNGVAU055
Active

Schneider Electric TeSys Deca frame 2 undervoltage release (MN), GVAU055, 48V AC 50Hz control circuit, 690V rated insulation, set of 10.

StockContact for availability
Lead timeIn Stock wk
MOQ1 pcs
Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Jul 2026
How we verify every order →

Specifications

Mechanical

GVAU055 — Mechanical
ParameterValue
Height89 mm
Width18 mm
Depth66 mm

Product details

The GVAU055 is an undervoltage release (MN) for Schneider Electric's TeSys Deca frame 2 motor starters and breakers. It drops the main contacts when the control voltage falls to between 0.7 and 0.35 of the rated Un, preventing automatic restart after a brownout or power loss — standard practice for conveyor lines, pumps, and any load where unexpected re-energization is a safety or equipment risk. Rated for a 48 V AC 50 Hz control circuit, with an operating range of 0.85 to 1.1 Un, so it holds in through moderate dips but releases cleanly before the motor contactor drops out. Insulation voltage rated 690 V AC per IEC 60947-1, and 600 V AC per UL 60947-4-1 and CSA C22.2 No 60947-4-1 — covers the vast majority of 400 V and 480 V motor circuits without derating.

The 1.4 N·m tightening torque on the screw-clamp terminals is the same as the rest of the Deca range, so panel wiring practices carry over.

DIN-rail mount, 18 mm wide, 89 mm tall, 66 mm deep. Fits the standard TeSys Deca frame 2 footprint — snaps directly onto the left side of a GV2ME, GV2P, GV3P, or GV3L breaker. No extra DIN space required beyond the breaker itself. Screw-clamp terminals accept 1 to 2.5 mm² solid or 0.75 to 2.5 mm² flexible, with or without ferrules. Strip length follows the standard Deca practice — the same tooling and wire prep as the breaker's own terminals. Mechanical durability is rated 10,000 cycles with GV3P and GV3L breakers, 30,000 cycles with GV2ME and GV2P. The difference comes from the internal mechanism of each breaker family — the GV2 series is lighter, so the release sees less shock per cycle.

Power draw and thermal

Inrush power is 8 W / 12 VA AC at pickup; hold-in drops to 1.1 W / 3.5 VA AC. The 100% on-load factor means it can stay energized continuously — no duty-cycle derating needed for a permanently powered control circuit.

Frequently asked questions

What is the closest alternative to GVAU055 in the TeSys Deca family?

Within the same TeSys Deca frame 2, the only difference between undervoltage release variants is the control voltage. The GVAU series covers 24 V AC, 48 V AC (this part), 110 V AC, 230 V AC, 400 V AC, and 24 V DC. If your control circuit is not 48 V AC 50 Hz, pick the GVAU variant matching your voltage — the mechanical fit and wiring footprint are identical across the series.

What compliance documentation does Schneider provide for GVAU055?

The GVAU055 carries IEC 60947-1 certification for operating time and rated insulation voltage, plus UL 60947-4-1 and CSA C22.2 No 60947-4-1 for North American installations. RoHS and REACH compliance is standard for the TeSys Deca range.

What is the depth dimension of GVAU055?

66 mm depth, 18 mm width, 89 mm height. The 18 mm width is one standard DIN module, so it occupies one slot alongside the breaker.

MPN
GVAU055