Skip to main content
Schneider Electric GVAU056 — Motor Protection Circuit Breakers (MPCB)

Schneider GVAU056 TeSys Undervoltage Release, 48V AC 60Hz

MPNGVAU056
Obsolete

Schneider Electric TeSys Deca undervoltage release, GVAU056, 48V AC 60Hz, screw clamp terminals, set of 10.

StockContact for availability
MOQ1 pcs
Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Jul 2026
How we verify every order →

Specifications

Mechanical

GVAU056 — Mechanical
ParameterValue
Height89 mm
Width18 mm
Depth66 mm

Product details

It operates on a 48 V AC 60 Hz control circuit, with a tripping threshold of 0.7 to 0.35 times the rated control voltage (Un).

The rated insulation voltage (Ui) is 690 V AC per IEC 60947-1, 600 V AC per UL 60947-4-1 and CSA C22.2 No 60947-4-1. The control voltage limits are 0.85 to 1.1 Un, so the release holds in reliably as long as the 48 V supply stays between roughly 40.8 and 52.8 V AC. Inrush power draw is 8 W / 12 VA AC, dropping to 1.1 W / 3.5 VA AC holding. That low hold-in draw means the control transformer can be sized for the inrush peak without oversizing for continuous load. Mechanical durability is rated at 10,000 cycles with GV3P and GV3L breakers, and 30,000 cycles with GV2ME and GV2P — the release itself is robust, but its service life depends on the host breaker model. Screw clamp terminals accept 1 to 2.5 mm² solid or 0.75 to 2.5 mm² flexible wire, with or without ferrules. Tightening torque is under 1.4 N.m. The 18 mm width matches the standard TeSys Deca modular footprint, so it snaps onto the same DIN rail alongside the breaker or contactor.

The GVAU056 is classified as obsolete by the manufacturer.

This release mounts directly onto TeSys Deca breakers (GV3P, GV3L, GV2ME, GV2P) and contactors. It occupies one 18 mm module width on the DIN rail. The 66 mm depth and 89 mm height are standard for the accessory footprint, so it does not extend beyond the host device envelope. Wiring is straightforward: the two screw terminals connect to the 48 V AC control circuit; no auxiliary power supply is needed.

Frequently asked questions

What are the key electrical ratings of the GVAU056?

Control voltage is 48 V AC 60 Hz. Tripping threshold is 0.7 to 0.35 Un. Rated insulation voltage is 690 V AC (IEC) / 600 V AC (UL/CSA). Inrush power is 8 W / 12 VA AC; hold-in power is 1.1 W / 3.5 VA AC.

What is the mechanical durability of the GVAU056?

Mechanical durability is 10,000 cycles with GV3P and GV3L breakers, and 30,000 cycles with GV2ME and GV2P breakers.

What wire sizes and torque does the GVAU056 accept?

Screw clamp terminals accept 1 to 2.5 mm² solid or 0.75 to 2.5 mm² flexible wire (with or without ferrules). Tightening torque is under 1.4 N.m.

MPN