HMIYP6M2ETH — Specifications
ParameterValue
Range of productHarmony P6
Relative humidity10...90 % non condensing
Product or component typeEthernet interface module
Integrated connection typeM.2 1 RJ45 jack 10 BASE-T/100 BASE-TX/1000 BASE-T IEEE 1588 supported
Accessory (separate part category)Connection accessory
Ambient air temperature for storage-4...140 °F (-20...60 °C)
Ambient air temperature for operation32...131 °F (0...55 °C)

Product details

What this module does in the panel

The HMIYP6M2ETH is a Harmony P6 Ethernet interface module — a connection accessory that adds a single RJ45 GbE port with IEEE 1588 precision time protocol to the HMI or industrial PC. It expands the base unit's networking capability without consuming an internal slot; it mounts as an external expansion option on the rear of the Harmony P6 display or box PC. The port handles 10/100/1000 BASE-T and supports IEEE 1588v2, so it's suited for applications that need synchronized timestamping across distributed I/O or drives — packaging lines, printing presses, or any motion axis where coordinated events matter.

Environmental limits that matter

Rated for 32 to 131 °F (0 to 55 °C) operating ambient, with storage from -4 to 140 °F (-20 to 60 °C). Non-condensing humidity range of 10 to 90 %. That covers most control cabinets and conditioned shop floors; if the panel sits in a hot attic or near a furnace, watch the upper operating limit.

What the IEEE 1588 support means

IEEE 1588 (Precision Time Protocol) on this port lets the Harmony P6 act as a clock slave or master in a synchronized network. That matters when multiple HMIs or controllers need to share a common timebase for event logging, alarm sequencing, or coordinated motion. Without it, NTP gives millisecond accuracy; with it, sub-microsecond sync is possible on the same cable.

Frequently asked questions

What is HMIYP6M2ETH used for?

It's an Ethernet interface module that adds a GbE RJ45 port with IEEE 1588 precision timing to a Harmony P6 HMI or industrial PC. You bolt it on as an external expansion option when the base unit needs an extra network drop or synchronized clocking.

Where can I buy HMIYP6M2ETH and what is the lead time?

Sourced and quoted to order against an RFQ through independent distribution. Availability and current pricing are confirmed at quote time — no runaround, no phantom stock.

What is the operating temperature range for this module?

Rated for 32 to 131 °F (0 to 55 °C) operating, and -4 to 140 °F (-20 to 60 °C) storage. Keep it in that band and it'll run without derating.