The LA1KN113M is a TeSys K auxiliary contact block — 1 NO + 1 NC instantaneous contacts, front-mounted onto a contactor or starter base (EN 50012 profile). Spring-cage terminals accept 0.75…1.5 mm² flexible or rigid cable. It is rated 10 A conventional free-air thermal current (Ith) at 50 °C, with a rated insulation voltage (Ui) of 690 V per IEC 60947-5-1 and 600 V per UL/CSA. Lifecycle: this order code is marked obsolete. There is no official successor listed on the record, so any replacement must be verified against the existing panel layout — contact rail spacing, terminal style, and the front-mounting footprint.
Integration and mounting constraints
Mounts on the front of a TeSys K contactor or reversing starter. Spring terminals — no screw torque to check, but the strip length needs to be clean 8 mm to avoid whiskers under the cage. The 690 V AC insulation (25…400 Hz) covers 480 V and 600 V line-to-line systems with margin.