Schneider Electric LA1LC071FC — Motor Control Accessories

Schneider LA1LC071FC TeSys Shunt Trip, 120 V AC, Obsolete

MPNLA1LC071FC
Obsolete

Schneider TeSys LA1LC071FC, shunt trip, 120 V AC 60 Hz, without time delay, set of 10.

Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Jul 2026

Specifications

LA1LC071FC — Identification
ParameterValue
Product / component typeShunt trip
Product rangeTeSys
LA1LC071FC — Other specifications
ParameterValue
Time delayWithout time delay
Operating time>= 10 ms
Quantity per setSet of 10
Device short nameLA1LC
Inrush power in8 VA AC
Voltage release typeInstantaneous Shunt trip
Threshold tripping voltage0.35...0.7 Uc
Coil voltage120 V AC 60 Hz
Control circuit voltage limits0.7...1.1 Uc
Hold-in power consumption in4 VA AC

Product details

The Schneider TeSys LA1LC071FC is a shunt trip — an instantaneous voltage release that trips a circuit breaker or contactor when its control voltage is applied. It operates on a 120 V AC 60 Hz control circuit, with a threshold tripping voltage of 0.35 to 0.7 Uc and a control voltage tolerance of 0.7 to 1.1 Uc. The operating time is at least 10 ms, and it has no intentional time delay. It is supplied as a set of 10 units.

The 120 V AC 60 Hz control voltage is the coil rating — apply that to trip the shunt. The 0.35 to 0.7 Uc threshold means the trip will initiate when the voltage drops to between 42 V and 84 V, which is typical for undervoltage release coordination. The inrush power draw is 8 VA AC, and hold-in power is 4 VA AC — small enough that the control transformer sizing is rarely a concern. The set of 10 is the factory packaging; if you need fewer, you will have to break the pack.

Frequently asked questions

What is the listed range for LA1LC071FC?

It belongs to the TeSys range, which covers motor control and protection components from Schneider Electric.

What is the time delay for this shunt trip?

It has no time delay — it is an instantaneous shunt trip. The operating time is at least 10 ms from application of control voltage.

MPN
LA1LC071FC