Skip to main content
Schneider Electric LADR29 — Motor Control Accessories

Schneider TeSys Deca LADR29 Off-Delay Auxiliary Block, 1-30s

MPNLADR29
Obsolete

Schneider Electric TeSys Deca LADR29, off-delay auxiliary contact block, 1NO+1NC, 1-30 s time delay range, Faston terminals, IP20.

Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Jul 2026

Specifications

LADR29 — Identification
ParameterValue
Product / component typeTime delay auxiliary contact block
Product rangeTeSys TeSys Deca
LADR29 — Electrical
ParameterValue
Rated operational voltage (Ue)690 V AC 25...400 Hz
Pole / contact composition1 NO + 1 NC
LADR29 — Cable & Connector
ParameterValue
Terminal connection capacityFaston terminals
LADR29 — Mechanical
ParameterValue
Width1.7 in (44 mm)
Height1.9 in (48 mm)
Depth2.4 in (61 mm)
LADR29 — Environmental
ParameterValue
IP protection ratingIP20 conforming to IEC 60529
Operating ambient temperature-40...158 °F (-40...70 °C)
Storage ambient temperature-76...176 °F (-60...80 °C)
Operating altitude3000 m
Environmental classNormal environment

Product details

The Schneider Electric TeSys Deca LADR29 is an off-delay auxiliary contact block with 1 normally open and 1 normally closed pole, designed for front mounting on TeSys Deca contactors or reversing starters. The time delay range is adjustable from 1 to 30 seconds, and the contacts are rated for 6 A at 120 V AC-15 (inductive) and 0.55 A at 125 V DC-13.

The off-delay function means the NC contact changes state immediately on coil de-energisation, then the NO contact returns to its rest position after the set delay — useful for sequencing motor starter drop-out or staging fan coast-down. The 1.5 ms non-overlap time between NC and NO on both energisation and de-energisation ensures break-before-make, preventing momentary cross-conduction in reversing or star-delta circuits. Termination is via Faston connectors (0.25 in / 6.35 mm tabs), common for panel wiring with pre-crimped leads or quick-connect receptacles.

Mounts on the front of a TeSys Deca contactor or reversing starter, adding time-delay auxiliary contacts without increasing the contactor's panel depth. The block dimensions are 1.7 in wide × 1.9 in high × 2.4 in deep (44 × 48 × 61 mm).

Frequently asked questions

What is the time delay range and contact configuration?

The LADR29 provides an off-delay adjustable from 1 to 30 seconds, with 1 normally open and 1 normally closed contact.

What are the rated operational currents?

Rated operational current is 6 A at 120 V AC-15 (inductive load), 1.04 A at 690 V AC-15, 0.55 A at 125 V DC-13, and 0.1 A at 600 V DC-13.

What approvals or compliance documentation does this part carry?

The LADR29 is rated with insulation voltage per IEC 60947-5-1, UL 60947-5-1, and CSA C22.2 No 60947-5-1. The protective treatment is TH per IEC 60068.

MPN
LADR29