Skip to main content
Schneider Electric LADR49 — Motor Control Accessories

Schneider TeSys Deca LADR49 Time Delay Block, Off Delay 10-1

MPNLADR49
Obsolete

Schneider Electric TeSys Deca LADR49, time delay auxiliary contact block, 1NO+1NC, off delay 10-180s, front mounting, Faston terminals.

Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Jul 2026

Specifications

LADR49 — Identification
ParameterValue
Product / component typeTime delay auxiliary contact block
Product rangeTeSys TeSys Deca
LADR49 — Electrical
ParameterValue
Rated operational voltage (Ue)690 V AC 25...400 Hz
Pole / contact composition1 NO + 1 NC
LADR49 — Cable & Connector
ParameterValue
Terminal connection capacityFaston terminals
LADR49 — Mechanical
ParameterValue
Width1.7 in (44 mm)
Height1.9 in (48 mm)
Depth2.4 in (61 mm)
LADR49 — Environmental
ParameterValue
IP protection ratingIP20 conforming to IEC 60529
Operating ambient temperature-40...158 °F (-40...70 °C)
Storage ambient temperature-76...176 °F (-60...80 °C)
Operating altitude3000 m
Environmental classNormal environment

Product details

It provides one normally-open and one normally-closed contact (1NO+1NC) with an adjustable off delay from 10 to 180 seconds, meaning the NC contact holds its state for that set period after the coil de-energises before dropping out. Rated operational current is 6 A at 120 V AC-15 and 0.55 A at 125 V DC-13, with a conventional free-air thermal current of 10 A at 60 °C. Insulation voltage is 690 V per IEC 60947-5-1, 600 V per UL and CSA equivalents. Faston terminals make for quick wiring on the bench or during panel assembly.

The off-delay range of 10 to 180 seconds covers most sequencing and anti-overlap timing needs in motor starter circuits — fan coast-down delays, pump-off timers, or interlock release after a stop command. The 1.5 ms non-overlap time on both energisation and de-energisation ensures the NC and NO contacts never bridge simultaneously, which is critical for safety interlock circuits that must break before make. Mechanical durability is 5 million cycles — a solid figure for a timer block that sees regular cycling in HVAC or conveyor applications. Minimum switching requirements of 5 mA and 17 V mean this block can handle dry-contact PLC inputs without wiper-burn issues — useful when the timer feeds a digital input card rather than a power circuit.

Frequently asked questions

What is the closest alternative to the LADR49 in the TeSys Deca family?

There is no official successor order code listed for the LADR49. For a pin-compatible drop-in, you would need to evaluate current TeSys Deca time delay blocks against the same Faston terminal pattern and front-mounting footprint — the off-delay function and 1NO+1NC contact arrangement are the critical fit parameters.

What are the key ratings for the LADR49?

Off delay adjustable 10-180 s, 1NO+1NC contacts, rated operational current 6 A at 120 V AC-15 and 0.55 A at 125 V DC-13, conventional thermal current 10 A at 60 °C, insulation voltage 690 V IEC / 600 V UL/CSA, IP20 protection, Faston terminals.

MPN